Commissioning
EL3783
131
Version: 1.1
Input channel 1
Index
Index
50 V
0x01
hex
, (Limit 1, limit value undershot)
0x01
hex
, (Limit 2, limit value undershot)
100 V
0x03
hex
, (Limit 1, limit value reached)
0x01
hex
, (Limit 2, limit value undershot)
150 V
0x02
hex
, (Limit 1, limit value exceeded)
0x01
hex
, (Limit 2, limit value undershot)
210 V
0x02
hex
, (Limit 1, limit value exceeded)
0x02
hex
, (Limit 2, limit value exceeded)
4. Provision in the process data
The influencing parameters can be changed in the CoE of the respective channel.
Fig. 171: User settings and vendor calibration in the CoE online directory
Changes in the CoE directory
In case of changes to the CoE default parameters, it is essential that corresponding values are en-
tered in the start-up list, so that in the case of exchange the EL3783 operates again as foreseen in
the application.
Predefined PDO Assignment
The "Predefined PDO Assignment" enables a simplified selection of the process data.
The desired function is selected on the lower part of the "Process Data" tab. As a result, all necessary PDOs
are automatically activated and the unnecessary PDOs are deactivated.
8 PDO assignments are available: