Commissioning
EL37x2
156
Version: 3.5
Typification of the 2/3/4-wire connection of current sensors
Current transducers/sensors/field devices (referred to in the following simply as ‘sensor’) with the industrial
0/4-20 mA interface typically have internal transformation electronics for the physical measured variable
(temperature, current, etc.) at the current control output. These internal electronics must be supplied with
energy (voltage, current). The type of cable for this supply thus separates the sensors into
self-supplied
or
externally supplied
sensors:
Self-supplied sensors
• The sensor draws the energy for its own operation via the sensor/signal cable + and -.
So that enough energy is always available for the sensor’s own operation and open-circuit detection is
possible, a lower limit of 4 mA has been specified for the 4-20 mA interface; i.e. the sensor allows a
minimum current of 4 mA and a maximum current of 20 mA to pass.
• 2-wire connection see Fig.
2-wire connection
, cf. IEC60381-1
• Such current transducers generally represent a current sink and thus like to sit b and – as a
‘variable load’. Refer also to the sensor manufacturer’s information.
Fig. 197: 2-wire connection
Therefore, they are to be connected according to the Beckhoff terminology as follows:
preferably to
‘single-ended’ inputs
if the +Supply connections of the terminal/ box are also to be used -
connect to +Supply and Signal
they can, however, also be connected to
‘differential’ inputs
, if the termination to GND is then
manufactured on the application side – to be connected with the right polarity to +Signal and –Signal
It is important to refer to the information page
Configuration of 0/4..20 mA differential inputs
(see
documentation for the EL30xx terminals, for example)!
Externally supplied sensors
• 3- and 4-wire connection see Fig.
Connection of externally supplied sensors
, cf. IEC60381-1
• the sensor draws the energy/operating voltage for its own operation from 2 supply cables of its own.
One or two further sensor cables are used for the signal transmission of the current loop:
◦ 1 sensor cable: according to the Beckhoff terminology such sensors are to be connected to
‘single-ended’ inputs
in 3 cables with +/-/Signal lines and if necessary FE/shield
◦ 2 sensor cables: for sensors with 4-wire connection based on +supply/-signal/-signal,
check wsignal can be connected to +supply or –signal to –supply.
- Yes: then you can connect accordingly to a Beckhoff
‘single-ended’ input
.
- No: the Beckhoff
‘differential’ input
for +Signal and –Signal is to be selected; +Supply and –
Supply are to be connected via additional cables.
It is important to refer to the information page
Configuration of 0/4..20 mA differential inputs
(see documentation for the EL30xx terminals, for example)!
Note: expert organizations such as NAMUR demand a usable measuring range <4 mA/>20 mA for error
detection and adjustment, see also NAMUR NE043.
The Beckhoff device documentation must be consulted in order to see whether the respective device
supports such an extended signal range.
Usually there is an internal diode existing within unipolar terminals/ boxes (and related product groups), in
this case the polarity/direction of current have to be observed.
Содержание EL3702
Страница 1: ...Documentation EL37x2 2 channel Analog Input Terminals with oversampling 3 5 2017 06 23 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EL37x2 6 Version 3 5...
Страница 83: ...Commissioning EL37x2 83 Version 3 5 Fig 92 Incorrect driver settings for the Ethernet port...
Страница 142: ...Commissioning EL37x2 142 Version 3 5 Fig 184 Process data tab SM0 EL37x2...
Страница 143: ...Commissioning EL37x2 143 Version 3 5 Fig 185 Process data tab SM1 EL37x2...
Страница 150: ...Commissioning EL37x2 150 Version 3 5 Fig 193 Process Data tab adaptation of process data in SM0...