Commissioning
EL37x2
125
Version: 3.5
The Task have to be inserted as “TwinCAT Task With Image” and also creates an “Inputs” and “Outputs”
folder therefore. The properties of the new (or as the case may be already existing) task must have activated
the attribute “Create symbols” to make them selectable by the “Target Browser” of the Scope later on. The
task cycle time have to be changed if so. Then, with10 x Oversampling 1 ms at 100 µs base time, resulting
10 ticks will be set by the usage of the EL3751 for example:
Fig. 156: Task property "Create symbols" must be activated
There’s a default value given for the Port number (301) that should be changed, if necessary. This number
have to make acquainted for the Scope, if applicable, later on. By a right click on “Inputs” that oversampling
based variable can now be appended with the fitting datatype of an array. „ARRAY [0..9] OF DINT“ referred
to as „Var 1“ in this case:
Fig. 157: Insertion of variable "Var 1" fitting to the oversampling (-factor)
Step 3: Linking an array variable with an oversampling PDO
By right click on “MAIN.aUI_Samples” (according to the last preceding paragraph Step 2a) or rather
“Var 1” (according to the last preceding paragraph Step 2b) within the Solution Explorer a window opens to
select the process data:
Содержание EL3702
Страница 1: ...Documentation EL37x2 2 channel Analog Input Terminals with oversampling 3 5 2017 06 23 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EL37x2 6 Version 3 5...
Страница 83: ...Commissioning EL37x2 83 Version 3 5 Fig 92 Incorrect driver settings for the Ethernet port...
Страница 142: ...Commissioning EL37x2 142 Version 3 5 Fig 184 Process data tab SM0 EL37x2...
Страница 143: ...Commissioning EL37x2 143 Version 3 5 Fig 185 Process data tab SM1 EL37x2...
Страница 150: ...Commissioning EL37x2 150 Version 3 5 Fig 193 Process Data tab adaptation of process data in SM0...