Operation
EK1960
71
Version: 1.3.1
Channel Interface
Description
Both Deactivated
Both inputs are deactivated
Single-Channel 1 Activated
Channel 1: Single-channel evaluation
Channel 2: deactivated
Single-Channel 2 Activated
Channel 1: deactivated
Channel 2: Single-channel evaluation
Single-Channel Both Activated
Channel 1: Single-channel evaluation
Channel 2: Single-channel evaluation
Two-Channel
Both inputs are activated, and two-channel evaluation with
Discrepancy Time (ms)
If the
Two-Channel
evaluation is enabled, the corresponding
Discrepancy time (ms)
can be set in
milliseconds. For each input there is a setting to indicate whether the input should be evaluated as
Break
Contact (NC)
or
Make Contact (NO)
. When a variable or a connecting line is connected to the function block,
the corresponding channel is enabled automatically.
Fig. 71: Make Contact (NO) / Break Contact (NC) setting
These settings are also accessible for each individual port of an FB via the context menu item
Change InPort
Settings
.