Operation
EJ6910
90
Version: 1.7.0
Deactivation
Description
Permanent deactivation
The TwinSAFE group is permanently disabled by the user. The substitute values
parameterized for the group are set for the group outputs.
If this group is enabled again, the RUN signal for this group must change from 0
to 1, in order for the group to start.
Parameter:
Permanent Deactivation Allowed:
TRUE / FALSE
Deactivation until the
EL6910 is switched off
and back on again
The TwinSAFE group is disabled until the EL6910 is switched on again. The
substitute values parameterized for the group are set for the group outputs. This
setting cannot be used as default setting for the safety program download.
If this group is enabled again (other than by switching off and on again), the RUN
signal for this group must change from 0 to 1, in order for the group to start.
Parameter:
Temporary Deactivation Allowed
: TRUE / FALSE
Deactivation of manual
control unit
After starting the deactivation, the connection defined in the group must report a
COM error after a period of 10 seconds, for sample (default setting). If this is not
the case, a group error set and corresponding diagnostic message is generated.
Only one connection may be defined in the group, which must be a master
connection.
Parameter:
Passification Allowed
: TRUE / FALSE
Timeout Passification Allowed
: Time in ms
The customization can also be carried out during the download of the safety application.
In order to be able to perform a customization, the groups must be set accordingly. This is done via the
group properties.
Fig. 132: Properties of the TwinSAFE group
If one of the customization parameters (
Passification Allowed, Permanent Deactivation Allowed
or
Temporary Deactivation Allowed
) is set to TRUE, all outputs of the TwinSAFE group, which are not
SafetyAlias Devices, are listed in the list of
Replacement Values
. Here you can parameterize the substitute
values to be written to the output in the event of deactivation of the group.
Содержание EJ6910
Страница 1: ...Operation Manual for EJ6910 TwinSAFE Logic Module 1 7 0 2017 11 15 Version Date...
Страница 2: ......
Страница 54: ...Operation EJ6910 54 Version 1 7 0 Fig 64 The Safety Project Online View tab...
Страница 56: ...Operation EJ6910 56 Version 1 7 0 Fig 66 Group Status Online ERROR Fig 67 Group Status Online STOP...
Страница 93: ...Operation EJ6910 93 Version 1 7 0 Fig 138 Activate saving of all analog group inputs...
Страница 106: ...Appendix EJ6910 106 Version 1 7 0 5 2 Certificates...