Operation
EJ6910
69
Version: 1.7.0
Fig. 94: Execution order FBs
4.3.7.15
Direct mapping of local I/Os
If a TwinSAFE logic has local inputs and outputs, e.g. an EK1960, an assignment to safe and non-safe
signals can be made by the user via the
Internal Direct Mapping
tab of the alias device. These direct
assignments have the advantage that no logic program has to be created by the user for this purpose.
To use the internal direct mapping, the linking mode of the
Alias Device
must be set to local.
Fig. 95: Internal Direct Mapping
Typical applications are linking the ErrAck signal of the modules to a
Standard Alias Device
or switching an
output due to a safe input signal.
In the figure, the relay output
FSOUT relay modules Channel 1.Output
is switched by the safe input
Term
(15) (EL1904) - Module 1 (FSOES) InputChannel 1
.