EJ4018, EJ4024 - Technical data
Technical data
EJ4018
EJ4024
Connection technology
2-wire, single-ended
Number of outputs
8
4
Power supply
24 V
DC
via Up contacts
24 V
DC
via Signal distribution board
Signal current
0 mA .. 20 mA
4 mA .. 20 mA
Distributed Clocks (DC)
yes
Accuracy Distributed Clocks (DC)
<< 1 µs
Load
< 150 Ω
< 350 Ω
Measuring error
< 0.1 % (at 0°C .. +55°C, relative to full
scale value)
< ±0.2% (when using the extended temper-
ature range, relative to the full scale value)
< 0.1 % (relative to full scale value)
Resolution
12-bit
Electrical isolation
500 V (E-bus/signal voltage)
Conversion time
~ 400 µs
~ 250 µs
Current consumption load voltage (Up con-
tacts)
typ. 60 mA
typ. 25 mA
Current consumption via E-bus
typ. 80 mA
typ. 90 mA
Permissible ambient temperature range dur-
ing operation
-25 °C .. +60 °C (extended temperature
range)
0 °C .. +55 °C
Permissible ambient temperature range dur-
ing storage
-40 °C .. +85 °C
-25 °C .. +85 °C
Permissible relative air humidity
95 %, no condensation
Operating altitude
max 2,000 m
Dimensions (W x H x D)
approx. 12 mm x 66 mm x 55 mm
Weight
approx. 30 g
Mounting
on signal distribution board
Mounting position
Pollution degree
2
1 and 7
Color coding
blue
Vibration / shock resistance
conforms to EN 60068-2-6 /EN 60068-2-27 (with corresponding signal distribution
board)
EMC immunity / emission
conforms to EN 61000-6-2 /EN 61000-6-4 (with corresponding signal distribution board)
Protection class
EJ module: IP20
EJ system: dependent on the signal distribution board and housing
Approval
CE, UL
CE
CE approval
The CE Marking refers to the EtherCAT plug-in module mentioned above.
If the EtherCAT plug-in module is used in the production of a ready-to-use end product (PCB in con-
junction with a housing), the manufacturer of the end product must check compliance of the overall
system with relevant directives and CE certification.
To operate the EtherCAT plug-in modules, they must be installed in a housing.