Commissioning
CX20x0
42
Version: 2.5
6.3.1
Connect Embedded PC
The cables of an external voltage source are connected to the power supply unit with spring-loaded
terminals. Observe the required conductor cross-sections and strip lengths.
Table 28: Required conductor cross-sections and strip lengths.
Conductor cross-section
0.5 ... 2.5 mm
2
AWG 20 ... AWG 14
Strip length
8 ... 9 mm
0.33 inch
Fig. 24: Connection example with a CX20x0.
Connect the Embedded PC as follows:
1. Open a spring-loaded terminal by slightly pushing with a screwdriver or a rod into the square opening
above the terminal.
2. The wire can now be inserted into the round terminal opening without any force.
3. The terminal closes automatically when the pressure is released, holding the wire safely and
permanently.
ð
You have successfully connected the voltage source to the power supply terminal when the two upper
LEDs of the power supply terminal light up green.
The left LED (Us 24V) indicates the supply of the basic CPU module and the terminal bus. The right LED
(Up 24V) indicates the bus terminal supply via the power contacts.
6.3.2
UL requirements
The CX20x0 Embedded PCs are UL-certified. The corresponding UL label can be found on the name plate.
Содержание CX20 0 Series
Страница 1: ...Manual EN CX20x0 Embedded PC 11 10 2021 Version 2 5...
Страница 2: ......
Страница 5: ...Table of contents CX20x0 5 Version 2 5 List of tables 88 List of figures 90...
Страница 6: ...Table of contents CX20x0 6 Version 2 5...
Страница 91: ......