Troubleshooting
CPX27xx-0010
29
Version: 0.2
7
Troubleshooting
Pixel errors
Pixel errors in the TFT display are production-caused and represent no complaint- reason!
Anomalies of the Touchscreen
Anomalies of the touchscreen sensor are production-caused and represent no complaint-reason!
Fault
Cause
Measures
The Panel PC shows no function
No power supply to the Panel PC/
Industrial PC
Cable not connected
Check power supply cable
1. Correctly connect cable
2. Call Beckhoff Service
Computer boots, software starts, but
control does not operate correctly
Cause of the fault is either in the
software or in parts of the plant
outside the Industrial PC
Call the manufacturer of the
machine or the software
Malfunction of the touchscreen
Bad or missing ground connection of
the device
Establish ground connection
Bad or missing ground connection of
the user
User must stand on the floor
with ordinary shoes
USB error while TwinCAT access via
USB
Cycle time in TwinCAT is set on 10
ms (standard)
Increase the cycle time up to
50 ms till 80 ms
The Panel PC functions only partially
or only part of the time, e.g. no or
dark picture
Faulty backlight in the display
Defective components in the Panel
PC
Call Beckhoff Service
Call Beckhoff Service