Product Description
Protective Earthing (PE)
CAUTION
The protective conductor connection must not be used for other potentials. “PE” and
“0V” (24V system power supply) must be connected to the same potential (connected
in the control cabinet).
The wiring in the control cabinet must occur in accordance to the standard
EN 60204-1:2006 (PELV = Protective Extra Low Voltage).
EN 60204-1:2006 part 6.4.1: b): One side of the circuit or one point of the power
source must be connected to the protective earth conductor system.
Breaking the Power Supply/ Shutting down
CAUTION
Never disconnect the ground connection when switching off the device. Always
disconnect the 24V cable, other wise electricity can still flow due to the screen in
dependence of the device.
Any connected devices with its own power supply must have the same potential for
“PE” and “GND” like the Panel PC system (no potential difference).
2.5 Status LEDs
The Status LEDs are
located at the front side of
the C6030-0060:
Status LEDs
Description of the Status LEDs:
1
UPS Link
-
not defined
2
TC (TwinCAT):
red
blue
blue/ red blinking
green
green/ red blinking
TwinCAT Stop
TwinCAT Config
TwinCAT Config (Fieldbus Error)
TwinCAT Run
TwinCAT Run (Fieldbus Error)
3
Power:
green
yellow
Industrial PC is busy
Industrial PC shutdown
4
HDD (Hard disk):
red
access to the memory device
C6030-0060
11