Cable-cross-section for 
connection of power supply 

 
 
 
 
 
 
 
 

 

Warning 

 
 
 
 
 
 

PC_ON and power status 

 
 
 
 
 
 
 
 

 

Warning 

 
 
 
 
 
 
 
 

UPS output 

 
 
 
 
 
 

UPS output function 

 
 
 
 
 
 
 
 
 

Connecting Power Supply 

The external wiring consists of the connection of the power supply, the 
battery pack (optional) and the connection of customized components for 
shutting down the PC. 
 

Cable Cross Sections 

 
For the connection of the power supply, wiring with a cable-cross-section of 
1.5 mm

must be used.  

With bigger distances between voltage source and PC, you take the 
voltage drop as a function of the cable-cross-section as well as voltage 
fluctuations of your distribution voltage into account, so that is secured that 
the voltage doesn't fall under 22 V at the power supply. 
 
 

The power supply must be protected with maximum 16 A. 

 

Configuration for shutting down the PC 

 
The connections for shutting down the Industrial PCs are established via 
the 

PC_ON

 input and the 

Power Status

 output. 

 

PC_ON and Power Status functions 

 

 

If the 

PC_ON

 input is connected to 24 V via a switch, the PC shuts 

down according to the rules. The PC_ON signal is inverted, i.e. the 
PC shuts down if the 24 V connection is live. 

 

If the 

PC_ON

 input is 

NOT

 connected by the user, the PC can be 

booted in the familiar way by connecting the supply voltage and 
shut down via the battery by switching off the supply voltage. 

 

This procedure significantly reduces the service life of the 
rechargeable battery and should therefore not be used. 

 

 

Once the PC has shut down, the 

Power Status

 output is switched 

from 24 V to 0 V. Via this output a signal lamp can be connected or 
a contactor for de-energizing the whole system. The maximum 
load for the 

Power Status

 output is 0.5 A and a suitable fuse 

should be provided. 

 
UPS output 

 
In order to maintain a screen display for the PC in the event of a power 
failure, the power supply unit is equipped with a 

UPS output

 for connecting 

a Control Panel. The maximum load for the output is 1.4 A (max. 2.5 A 
from 2016 and later). 

UPS output function 

 

 

The 24 V DC connection at the UPS output is live even after a 

power failure. The maximum load is 1.4 A (max. 2.5 A from 2016 
and later). 

 

Once the PC has been de-energized via the UPS software, the 

UPS output

 is switched to 0 V. Any connected panel is thus 

switched off, and total discharge of the rechargeable battery is 
prevented. 

 

Содержание C3620

Страница 1: ...Installation and Operating instructions for Build in Industrial PCs C3620 C3640 from 0060 Version 4 0 Date 2020 04 24...

Страница 2: ......

Страница 3: ...dditional plug in cards optional 9 3 Installation Instructions 10 Transport and Unpacking 10 Transport 10 Unpacking 10 Installation of the PC in the control cabinet 11 Earthing measures 11 Power Suppl...

Страница 4: ...khoff Service 21 6 Assembly dimensions 22 Industrial PC C3620 22 Industrial PC C3640 23 Mounting Opening 24 7 Appendix 25 Technical data 25 Approvals 25 FCC Federal Communications Commission Radio Fre...

Страница 5: ...er EtherCAT TwinSAFE and XFC are registered trademarks of and licensed by Beckhoff Automation GmbH Other designations used in this publication may be trademarks whose use by third parties for their ow...

Страница 6: ...are intended to alert the reader to the associated safety instructions Danger This symbol is intended to highlight risks for the life or health of personnel Warning This symbol is intended to highligh...

Страница 7: ...pment that have been switched off must be secured against being switched on again Danger Displays used for the PCs LC display are operated with a voltage of up to 1000 V depending on type For that rea...

Страница 8: ...ain legible National regulations depending on the machine type Depending on the type of machine and plant in which the Industrial PC is being used there will be national regulations for the control of...

Страница 9: ...ows the front of the PC with TFT display can be opened thus providing access to the drive optional 3 hard disk processor memory and plug in cards An ATX motherboard with seven slots for plug in cards...

Страница 10: ...ith seven slots for plug in cards is located behind the removable card holder and the swivel mounted power supply unit The connections of the Industrial PC to the outside are located on top of the hou...

Страница 11: ...ctors X112 X113 allow the PC to be connected to a 10 100 1000BASE T Local Area Network LAN DVI D Digital Visual Interface DVI out The DVI connectors X114 X115 are used for transferring the video signa...

Страница 12: ...eme variations in temperature make sure that moisture condensation does not form on or inside the device Prior to operation the unit must be allowed to slowly adjust to room temperature Should condens...

Страница 13: ...not be exposed to direct sunlight When the unit is in its mounting position the ventilation openings must not be obstructed Warning Extreme environmental conditions should be avoided as far as possibl...

Страница 14: ...ge CSA 300 V Current EN A 12 A Current CSA A 15 A Length of stripped conductor 8 to 9 mm Power Supply Configuration Supplied mains power unit The Industrial PCs is either fitted with a 100 240 VAC 50...

Страница 15: ...signments on the top of the female plug connector The minimum permitted conductive cross section is 1 5 mm fused for 10 A AWG 16 Industrial PCs with 100 240 VAC 50 60 Hz power supply unit Pin assignme...

Страница 16: ...mm Minimum conductor cross section AWG 16 Rated voltage EN 250 V Rated voltage CSA 300 V Current EN 16 A Current CSA 15 A Length of stripped conductor 8 to 9 mm Fitting the connector to the cable The...

Страница 17: ...ng to the rules The PC_ON signal is inverted i e the PC shuts down if the 24 V connection is live If the PC_ON input is NOT connected by the user the PC can be booted in the familiar way by connecting...

Страница 18: ...diagram external switch and power supply Wiring diagram Wiring according to the wiring diagram the circuit of PC_ON and Power Status is symbolical Connection of the Battery Pack and UPS Output only i...

Страница 19: ...ustrial PC and to the devices that are to be connected Connect all data transfer cables if present to the appropriate plug in receptacles of the data telecommunication networks Reconnect all devices t...

Страница 20: ...writing a file to the hard disk the file will be destroyed Control software typically writes something to the hard disk every few seconds so that the probability of causing damage by switching off whi...

Страница 21: ...losion Replace battery only with the identical type or an alternative type recommended by the manufacturer Notice correct polarity Danger Handling of Lithium Batteries Lithium Batteries should not be...

Страница 22: ...al Setup settings are incorrect Other cause Remove CD and press any key Check the setup settings Call Beckhoff Service Computer boots software starts but control does not operate correctly Cause of th...

Страница 23: ...lshorstweg 20 D 33415 Verl Germany Phone 49 0 5246 963 0 Fax 49 0 5246 963 198 e mail info beckhoff com Beckhoff Support Support offers you comprehensive technical assistance helping you no only with...

Страница 24: ...ly dimensions 22 C3620 C3640 Assembly dimensions Industrial PC C3620 Warning The assembly of the unit must take place with the orientation diagrammed here All dimensions in mm front view left view rea...

Страница 25: ...Assembly dimensions C3620 C3640 23 Industrial PC C3640 Warning The assembly of the unit must take place with the orientation diagrammed here All dimensions in mm front view left view rear view...

Страница 26: ...Assembly dimensions 24 C3620 C3640 Mounting Opening A mounting opening according to the following diagram is required Mounting opening for C3620 Mounting opening for C3640...

Страница 27: ...resistance according to EN 61000 6 2 Emitted resistance according to EN 61000 6 4 Transport and storage The same values for atmospheric humidity and shock resistance are to be observed during transpo...

Отзывы: