Error handling and diagnosis
BK9053, BK9103
40
Version: 2.3.0
7
Error handling and diagnosis
7.1
Diagnostic LEDs
After switching on, the Bus Coupler immediately checks the connected configuration. Error-free start-up is
indicated when the red
I/O ERR
LED goes out. If the
I/O ERR
LED blinks, an error in the area of the
terminals is indicated. The error code can be determined from the frequency and number of blinks. This
permits rapid rectification of the error.
The Bus Coupler has two groups of LEDs for the display of status. The upper group with four LEDs indicates
the status of the respective fieldbus. The significance of the fieldbus status LEDs is explained in the
appropriate sections of this manual. It corresponds to the usual fieldbus display.
On the upper right hand side of the Bus Couplers are two more green LEDs that indicate the supply voltage.
The left hand LED indicates the presence of the 24 V supply for the Bus Coupler. The right hand LED
indicates the presence of the supply to the power contacts.
Fig. 23: LEDs of Bus Couplers BK9053 and BK9103
LEDs for power supply diagnostics
LED
Meaning
LED Us
off
the power supply voltage, Us, is not present
on
the power supply voltage, Us, is present
LED Up
off
Supply voltage Up (for power contacts) not available
on
Supply voltage Up (for power contacts) available
LEDs at RJ45
LED
Meaning
LED Link/Act
off
No physical connection present
on
Physical connection present
flashing
Communication available
LED 10/100 Mbaud
(only BK9103)
off
10 Mbaud (if LED Link/Act is lit or flashes)
on
100 Mbaud