Parameterization and commissioning
BK11x0, BK1250
67
Version: 4.1
Index 4012 Coupler Table 9 [LO]: Configuration of the Bus Terminal block
Index (hex)
Name
Meaning
Flags
Default
4012:0
Coupler Table 9 [LO]
Length of this object
RO
max. 128
4012:01
Subindex 001
Register 0: Name of the Bus Coupler
RO
0x0460 (1120
dec
1
)
4012:02
Subindex 002
Register 1: Name of the first terminal
RO
e.g.: 0x8201
(33281
dec
2
)
4012:03
Subindex 003
Register 2: Name of the 2
nd
terminal
RO
e.g.: 0x0BBA
(3002
dec
1
)
4012:04
Subindex 004
Register 3: Name of the 3
rd
terminal
RO
e.g.: 0x0C84 (3204
dec
1
)
4012:80
Subindex 128
Register 127: Name of the 127
th
terminal
RO
1
) For Bus Coupler and intelligent (e.g. analog) terminals, the terminal designation is
specified decimally in plain text; e.g. 0x0C84 (3204
dec
) means KL3204.
2
) For simple (digital) terminals, the following coding applies:
Bit
Value
Meaning
15
0
bin
intelligent (e.g. analog) terminal
1
bin
simple (digital) terminal
14...8
xxxxxx
bin
terminal size in bit (range of values: 0 to 63 bit)
7
1
bin
Shift register extension for Control Panels
6...3
0
bin
reserved
2
1
bin
KL1212
1
1
bin
Output terminal
Special case: 00
bin
means KL1202 or KL2212 (digital termi-
nals with input and output data)
0
1
bin
Input terminal
Index 4013 Coupler Table 9 [HI]: Configuration of the Bus Terminal block (continuation if more than
127 terminals)
Index (hex)
Name
Meaning
Flags
Default
4013:0
Coupler Table 9 [HI]
Length of this object
RO
max. 128
dec
4013:01
Subindex 001
Register 128: Name of the 128
th
terminal
RO
4013:02
Subindex 002
Register 129: Name of the 129
th
terminal
RO
4013:04
Subindex 128
Register 255: Name of the 255
th
terminal
RO
Index 40B4 Coupler Table 90 [LO]: Internal diagnostic information for the Bus Coupler
Index (hex)
Name
Meaning
Flags
Default
40B4:0
Coupler Table 90 [LO] Length of this object
RO
128
dec
40B4:01
Subindex 001
Register 0: reserved
RO
40B4:02
Subindex 002
Register 1: reserved
RO
40B4:04
Subindex 128
Register 127: reserved
RO
Index 40B5 Coupler Table 90 [HI]: Internal diagnostic information for the Bus Coupler (cont.)
Index (hex)
Name
Meaning
Flags
Default
40B5:0
Coupler Table 90 [HI]
Length of this object
RO
128
dec
40B5:01
Subindex 001
Register 128: reserved
RO
40B5:02
Subindex 002
Register 129: reserved
RO
40B5:04
Subindex 128
Register 255: reserved
RO
Index 40C4 Coupler Table 98 [LO]: Pd Update time (µs)
Index (hex)
Name
Meaning
Flags
Default
40C4:0
Coupler Table 98 Pd
Update time (µs)
Length of this object
RW
5
40C4:01
Min time
minimum update time on the K-bus
RW
0x0355 (853
dec
)
40C4:02
Max time
maximum update time on the K-bus
RW
0x059A (1434
dec
)
40C4:03
Curr time
current update time on the K-bus
RW
0x036A (874
dec
)
40C4:04
-
reserved
RW
0x0000 (0
dec
)
40C4:50
-
reserved
RW
0x09F8 (2552
dec
)