5.4
Error messages
Any errors that occur are shown in coded form by an error number in the LED display on
the front panel. All error messages result in the BTB/RTO contact being opened, and the
output stage of the amplifier being switched off (motor loses all torque). The motor-hol-
ding brake is activated.
Number Designation
Explanation
A/I/P/E
Status message
status message, no error, see page 65
. . .
Status Message
amplifier is updating the startup configuration
F00
no error
no error in the selected axis module
F01*
heat sink temperature
heat sink temperature too high
limit is set by manufacturer to 80°C
F02*
overvoltage
overvoltage in DC Bus link
limit depends on the mains supply voltage
F03*
following error
message from the position controller
F04
feedback
cable break, short circuit, short to ground
F05*
undervoltage
undervoltage in DC Bus link
limit is set by manufacturer to 100V
F06
motor temperature
motor temperature too high (or temp. sensor defect)
limit is set by manufacturer to145°C
F07
aux. voltage
internal aux. voltage not OK
F08*
overspeed
motor runs away, speed is too high
F09
EEPROM
checksum error
F10
Flash-EPROM
checksum error
F11
brake
cable break, short circuit, short to ground
F12
motor phase
motor phase missing (cable break or similar)
F13*
internal temperature
internal temperature too high
F14
output stage
fault in the output stage
F15
I²t max.
I²t max value exceeded
F16*
supply BTB/RTO
2 or 3 phases missing in the supply feed
F17
A/D converter
error in the analog-digital conversion
F18
regen
regen circuit faulty or incorrect setting
F19*
supply phase
a phase is missing in the supply power feed
F20
slot error
slot error
F21
handling error
software error on the expansion card
F22
earth/ground fault
not valid for this device
F23
CAN bus off
severe CAN bus communication error
F24
warning
warning display is evaluated as fault
F25
commutation error
commutation error
F26
limit-switch
homing error (drove onto hardware limit-switch)
F27
AS-option
not valid for this device
F28
reserve
reserve
F29
SERCOS error
only in SERCOS systems
F30
timeout
timeout, leads to emergency stop
F31
reserve
reserve
F32
system error
system software nor responding correctly
* = these error messages can be cleared without a reset, by using the ASCII command
CLRFAULT. If only one of these errors is present and the RESET button or the I/O
RESET function is used, only the CLRFAULT command will be executed.
66
AX2500 Installation Manual
Setup
02/06
Beckhoff
Содержание AX2500 Series
Страница 22: ...This page has been deliberately left blank 22 AX2500 Installation Manual Technical description 02 06 Beckhoff...
Страница 26: ...3 3 1 Dimensions 26 AX2500 Installation Manual Installation 02 06 Beckhoff AX250x and AX251x AX252x...
Страница 31: ...3 4 4 Connector assignments AX2500 Installation Manual 31 Beckhoff 02 06 Installation...
Страница 36: ...This page has been deliberately left blank 36 AX2500 Installation Manual Installation 02 06 Beckhoff...
Страница 60: ...This page has been deliberately left blank 60 AX2500 Installation Manual Interfaces 02 06 Beckhoff...
Страница 65: ...5 3 2 3 Status display on the master AX2500 Installation Manual 65 Beckhoff 02 06 Setup...
Страница 68: ...This page has been deliberately left blank 68 AX2500 Installation Manual Setup 02 06 Beckhoff...
Страница 81: ...This page has been deliberately left blank AX2500 Installation Manual 81 Beckhoff 02 06 Appendix...