background image

Documentation

Mains chokes AX2090-ND50

1.1
2015-11-11

Version:
Date:

Содержание AX2090-ND50

Страница 1: ...Documentation Mains chokes AX2090 ND50 1 1 2015 11 11 Version Date ...

Страница 2: ......

Страница 3: ...se 5 2 Safety 6 2 1 General safety instructions 6 2 1 1 Personel qualification 6 2 1 2 Description of safety symbols 6 2 2 Special safety instructions for AX2090 ND50 7 3 Installing the mains chokes 8 3 1 Circuit diagram 9 3 2 Dimensional drawing 9 4 Technical data 10 5 Support and Service 11 Mains chokes AX2090 ND50 3 Version 1 1 ...

Страница 4: ...his documentation Trademarks Beckhoff TwinCAT EtherCAT Safety over EtherCAT TwinSAFE XFC and XTS are registered trademarks of and licensed by Beckhoff Automation GmbH Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners Patent Pending The EtherCAT Technology is covered including but not limited to the...

Страница 5: ...he mains chokes of the series AX2090 ND50 are exclusively intended for application in the control cabinet as power supply unit of the AX5000 The chokes are installed together with the servo drive as components in electrical systems and machinery and may only be used in this way Mains chokes AX2090 ND50 5 Version 1 1 ...

Страница 6: ...mbol directly endangers the life and health of persons WARNING Caution Risk of injury Failure to follow the safety instructions associated with this symbol endangers the life ans health of persons CAUTION Personal injuries Failure to follow the safety instructions associated with this symbol can be lead to injuries to persons Attention Damage to the enviroment or devices Failure to follow the safe...

Страница 7: ...ant laws regulations and guidelines DANGER Serious risk of injury through electric shock Due to the DC link capacitors dangerous voltage 890VDC may persist at the DC link con tacts ZK and ZK DC and DC and RB and RB after the servo drive has been dis connected from the mains supply After disconnecting the servo drive wait at AX5101 AX5125 and AX520x 5 minutes at AX5140 AX5160 AX5172 15 minutes at A...

Страница 8: ...and measure the voltage on conductors L1 to L3 The device is safe once the voltage has fallen below 50 V CAUTION Caution Improper grounding Make sure when installing the mains chokes on a reasonable grounding The installation should be on a suitable for ground mounting plate chromated galvanized done Mounting Position the main choke on the mounting surface Mark out the positions of the threaded ho...

Страница 9: ... age at the DC link contacts ZK and ZK The device is safe once the voltage has fallen be low 50 V Connection Connect the protective conductor connection of the mains choke with the PE rail Connect the connecting cable of the mains choke to the appropriate terminals of the servo drive Connect the mains choke to the supply network 3 2 Dimensional drawing AX2090 ND50 Dimension mm 0060 0072 0090 0110 ...

Страница 10: ...ature 25 C to 70 C Protection IP00 Short circuit voltage UK 4 at 400 V 9 24 V UK 2 at 400 V 4 6 V Permissible contamination P2 to EN 61558 1 Thermal rating Ieff IN Recognition UL CSA 1 at mains frequency 60 Hz power loss approx 10 higher Three phase mains chokes AX2090 ND50 Data 0060 0072 0090 0110 0143 0170 Rated current A 60 72 90 110 143 170 Power loss total W 70 80 120 140 160 170 Inductance m...

Страница 11: ...uarters Beckhoff Automation GmbH Co KG Huelshorstweg 20 33415 Verl Germany Phone 49 0 5246 963 0 Fax 49 0 5246 963 198 e mail info beckhoff com Beckhoff Support Support offers you comprehensive technical assistance helping you not only with the application of individual Beckhoff products but also with other wide ranging services support design programming and commissioning of complex automation sy...