background image

Section: COMBUSTION AIR ADJUSTMENT PROCEDURE

28

Validate Safety Control Operation

 

Explosion, Fire, and 

Asphyxiation Hazard 

Testing by Qualified Technician Required. 

Failure to properly test and verify the 

correct function of operation and safety 

controls could lead to equipment malfunction.

The testing of operating and safety controls requires 

technical training and experience with power gas 

burners and appliances.

Carefully follow the manufacturer’s instructions supplied 

with the appliance and the controls.

Verify the correct function of all operating and safety 

controls used in the installation.

If instructions are not available, use the following 

recommended procedures and record all results in a 

start-up log.

1. 

High limit/ Pressure Control

 – To check the High 

Limit, raise the temperature or pressure of the 

operating control to a higher level and lower the 

limit to a setting less than the operating control. 

Run the burner until the high limit opens and shuts 

the burner off. Adjust the controls back to the 

desired settings.

2. 

Operating control

 – Run the burner until the 

operating control shuts it off. If necessary, make 

adjustments to ensure the control cycles the burner 

in the desired temperature or pressure range. 

3. 

Low water cutoff (LWCO)

 – With the burner firing, 

open the blow down valve on the low water cutoff, 

if applicable. As the water level drops, the LWCO 

switch contacts open and shut the burner off. When 

the water level rises, the LWCO contacts close 

and restart the burner. Monitor the LWCO switch 

operation in relation to the water level in the sight-

glass for synchronization.

4. 

Verify Flame Sensor Function

 – If 7590 operation 

sequence and function is correct, turn off power 

and remove sensor wire from bottom of 7590 

control.  Turn on power and fuel and initiate Call for 

Heat.  Verify that burner fires up and the gas valve 

closes.  After control locks out, flame shall go off. 

Combustion Air Adjustment 

Procedure

CO Leakage, Asphyxiation

Failure to maintain proper stack temperature could 

result in flue gas condensing and cause chimney 

damage.

Always use calibrated test 

instruments to set combustion 

levels. Verify that test instruments are calibrated and 

in good working condition.  If not already provided, 

drill test access holes in the flue pipe near the breech 

(or upstream of the boiler breech damper, if 

applicable) and in the front mounting plate area for 

firebox pressure.  Be careful not to damage any 

water-backed surface.  

1.  Initiate a call for heat. 

2.  Adjust the draft, over-fire, or breech pressure to the 

appliance manufacturer’s recommended level after 

flame has stabilized.

3.  Measure the carbon monoxide level and adjust 

air settings.  An operating range of 0 - 50 PPM is 

recommended for the CG10 burner.  

4.  Before making these tests, operate the burner to 

allow the heating system temperature to stabilize or 

nearly reach steady-state levels. 

5.  Measure the O

2

 or CO

2

 at the 50 PPM CO level.  It 

is recommended that you measure the oxygen (O

2

early in the test sequence because high levels of 

carbon monoxide (CO) can be created at very low 

or very high O

2

 levels.  The typical operating range 

is between 3%-5%.

6.  Open the air adjustment until the O

2

 level is 

increased by at least 1% or to 3% O

2

  (whichever 

is higher).  This should reduce the CO level and 

provide a margin of reserve air to accommodate 

variable conditions.

7.  Sample the CO level again.  It should be in the 0 to 

50 PPM range.

8.  Check the draft to ensure it still meets 

specifications.  If a major change in draft is required, 

repeat the above steps.

Содержание CG10-24

Страница 1: ...her flammable vapors and liquids in the vicinity of this or any other appliance WHATTO DO IFYOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in y...

Страница 2: ...Applications 6 Figure 4 Burner Configuration for 600 to 1200 MBH Applications 7 Figure 5 Gas Gun Assembly Component Familiarization 8 Figure 6 Vent Pipe with Draft Regulator 9 Figure 7 Chimney Design...

Страница 3: ...Keep this manual for your records and provide it to your qualified service agency for use in professionally setting up and maintaining your burner Your CG10 burner will provide years of efficient ope...

Страница 4: ...ic Direct Spark Motor Thermally Protected Manual Reset Combustion Air Proving Differential Pressure Switch Weight 40 lbs Mounting Orientation Up to 90 from upright with motor shaft horizontal Dimensio...

Страница 5: ...welded depending on application Figure 1 Burner Dimensions General Model Information Serial Number Including Date Code Rating Information Approval Agency Symbols R W Beckett Construction Setting Data...

Страница 6: ...t high rates Two air tube shrouds shape and stabilize the base of the flame Two burner head styles are available for each firing range to provide mixing control and retain the flame See Table 3 and Ta...

Страница 7: ...lower wheel Air Guide Chassis Firing Rate MBH Burner Head Blower Wheel Air Inlet Scroll Extension CG10B 601 756 10 4 6 31 dia x 2 42 w Part No 21339 Air Guide Part No 178 Installed 10 4S 757 952 10 5...

Страница 8: ...wires in location shown below see warning Electrical Shock and Explosion Hazard Failure to secure wires away from contact with the blower wheel could result in electrical shock or explosion hazard Ign...

Страница 9: ...t project into the chimney see Figure 6 Explosion Fire and Asphyxiation Hazard Wet or dusty environments could lead to blocked air passages corrosion damage to components impaired combustion performan...

Страница 10: ...inimum Clearence 2 FT NOTE Correct chimney design is shown by dotted lines Incorrect chimney design as shown by the solid lines may result in down drafts Figure 7 Chimney Design Above the Roof 5 Any l...

Страница 11: ...each opening in the enclosure should be 350 sq in 350 000 1 000 x 1 sq in 350 sq in A 350 sq in opening would typically be 12 x30 or 19 x19 Buildings with LessThan Adequate Air Infiltration If the bur...

Страница 12: ...and tables for pipe sizing as outlined in ANSI Z223 1 NFPA 54 All gas piping installation must comply with the latest edition of the National Fuel Gas Code ANSI Z223 1 NFPA 54 and other applicable loc...

Страница 13: ...5 590 800 1650 2700 4700 9700 40 130 245 500 760 1450 2300 4100 8300 50 115 215 440 670 1270 2000 3600 7400 60 105 195 400 610 1150 1850 3250 6800 70 96 180 370 560 1050 1700 3000 6200 80 90 170 350 5...

Страница 14: ...asket Verify that all boiler sections canopy and access plates or doors are fully equipped with gaskets and sealed against any leakage Mount the Burner The burner specified for packaged equipment will...

Страница 15: ...ve component that requires atmospheric air pressure to balance a diaphragm Vent lines must be run to the outdoors with the termination point away from fresh air intakes and windows The terminal openin...

Страница 16: ...al nipples Key Figure 10 thru Figure 12 Abbrev Item Description CGV HGPS LGPS MSC MLTC PRSSOV PRV SSOV1 SSOV2 TC TP U Combination Gas Valve High Gas Pressure Switch Low Gas Pressure Switch Main Shutof...

Страница 17: ...Major Components Explosion Fire and Asphyxiation Hazard This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes...

Страница 18: ...418 3226409U CG10 3S CG10 6S 3246705U 0 510 3226409U CG10 4S 3246706U 0 459 3226409U CG10 5S 3246707U 0 482 3226409U CG10 4 3246723U 0 547 3226409U CG10 5 3246724U 0 578 3226409U CG10 6 3246725U 0 59...

Страница 19: ...red in accordance with manufacturer s instructions Wire the burner in compliance with all instructions and diagrams provided by the appliance manufacturer Verify operation of all controls in accordanc...

Страница 20: ...A good ground is required to maintain a good flame sensing Use a ground fault interrupt if grounding of the burner can be compromised Explosion Fire and Asphyxiation Hazard Do not tamper with or bypas...

Страница 21: ...SURE Notes L1 power shall be run through the limits for high gas low gas LWCO high limit and operating control Solid lines factor wiring Dashed lines field wiring CONFIDENTIAL DRAWING PROPERTY OF R W...

Страница 22: ...AGRAM 7590WD02 DLW 09 01 15 7590 CONTROL RC 09 01 15 C NOT TO SCALE 1 OF 1 L1 L2 MOTOR L2 MTR IGNITER L2 IGN FLAME ROD WHITE ORANGE WHITE 7590 CONTROL TERMINAL TERMINAL COLOR IGNITER MOTOR BLUE W WHIT...

Страница 23: ...ATUS Status LED ON Pre purge FLAME MV STATUS Status LED Flashes Ignition FLAME MV STATUS Status MV LEDs On Run FLAME MV STATUS Status MV Flame LEDs On End Call for Heat FLAME MV STATUS LEDs Off Timers...

Страница 24: ...ach component i e 7590 sequence airflow proving switch ignition transformer gas valves safety lockout timing etc with the main shutoff cock closed monitor a complete burner run sequence Note that the...

Страница 25: ...10 1 3 6 1 8 10 1 4 1 2 1 10 3 900 CG10 5S 4 0 2 0 10 3 4 2 2 1 10 4 4 5 2 2 10 4 5 0 2 5 10 6 1000 CG10 6S 3 2 1 6 10 0 3 4 1 7 10 2 3 7 1 8 10 3 4 2 2 1 10 6 1100 CG10 6S 3 9 1 9 10 2 4 1 2 1 10 4...

Страница 26: ...6S CG10 5S CG10 4S CG10 3S CG10 2S CG10 1S 0 200 400 600 800 1000 1200 1400 0 1 2 3 4 5 Rate MBH Pressure Drop In WC CG10 6 CG10 5 CG10 4 CG10 3 CG10 2 CG10 1 Figure 19 Manifold to Furnace Pressure Dr...

Страница 27: ...urner 11 Check for leaks at the gas valve outlet pressure tap plug using a leak detection solution or soapsuds Bubbles forming indicate a leak SHUT OFF GAS AND FIX ALL LEAKS IMMEDIATELY If the burner...

Страница 28: ...function is correct turn off power and remove sensor wire from bottom of 7590 control Turn on power and fuel and initiate Call for Heat Verify that burner fires up and the gas valve closes After cont...

Страница 29: ...ion performance readings burner settings and appliance data on the start up form in the back of this manual If the burner is firing LP gas you must also record set up information on the propane conver...

Страница 30: ...t paying special attention to the air diffuser 8 Inspect the flame rod for oxidation or distortion Clean all surfaces set the probe position and insure that the flame rod is securely fastened Refer to...

Страница 31: ...nitor several burner start up cycles Verify prompt ignition and flame stability 4 Calculate the input firing rate and compare to the appliance specifications 5 Monitor the stack temperature Compare to...

Страница 32: ...fy burner model on adjustment scale Verify O ring is in place and lubricated Figure 23 Gas Gun Assembly Top View CG10 1S 10 6S CG10 3 10 6 CG10 1 10 2 END BELL MOTOR END BELL MOTOR 0 020 0 020 0 030 t...

Страница 33: ...5U 11 Air Band 5151503 12 24V Transformer 52310002U 13 Air Inlet Air Guide 300 600 MBH 189U Air Guide 600 1 000 MBH 178U Inlet Sleeve 32336U Item Description Beckett Part No 14 Blower Wheel CG10 300 6...

Страница 34: ...0 4 104U 10 4S 104SU 10 5 105U 10 5S 105SU 10 6 106U 10 6S 106SU 2 Spring Clamps 4 pack 3236501U 3 Electrode Set with Cable 10 4 10 6 22225U 10 1 10 3 2191201U 10 1S 10 6S 2191205U 4 Flame Rod with Ca...

Страница 35: ...eration Verified Temperature YES NO Pressure YES NO LWCO YES NO Other Limits YES NO n a Burner Fuel Natural Gas Propane Model ________________ Serial _________________________ Combustion Head ________...

Страница 36: ...copy of warranty form 61545 please choose one of the following options 1 Visit our website at www beckettcorp com warranty 2 Email your request to rwb customer service beckettcorp com 3 Write to R W...

Отзывы: