background image

19

CF1400/CF2300

 Burner Manual

Place the 

low-

fi

 re hold

 switch in the 

high-

fi

 re 

position

. The damper motor will begin to rotate 

after four seconds.
Use combustion test instruments to adjust the 
burner.

Adjust the air by moving the red cam to a lower 
number until a trace of smoke is achieved with 
CO

2

 level as high as possible (lowest possible 

O

2

).

Example

: 13.5% CO

2

 (2.5% O

2

) with a trace of 

smoke.

Increase the air by increasing the red cam 
number  to reduce CO

2

 by 2 percentage points 

at a zero smoke level. (Increase O

2

 by 3 

percentage points at a zero smoke level.) 
 

 

 

 

 

 

Example

: Reduce CO

2

 from 13.5% to 11.5%, 

with zero smoke (or increase O

2

 from 2.5% to 

5.5%).

A margin of reserve air has been added to 
accommodate variable conditions.

Check the breech draft pressure against the 
appliance manufacturer’s recommended setting 
(typ 0.1” W.C.).
If the breech pressure is higher or lower than 
recommended level, adjust the appliance breech 
damper to achieve the speci

fi

 ed setting. Recheck 

the smoke and CO

2

 levels. Adjust burner air if 

necessary.
Once all settings are complete and satisfactory, 
proceed to 

‘Set Low-

fi

 re Air’

.

Set Low-

fi

 re Air

Move the 

low-

fi

 re hold

 switch from the 

“High Fire 

position” 

to the 

“Low Fire Hold”

 position.

The damper will return to the 

low-

fi

 re

 air 

setting.

Check the smoke and CO

2

 (O

2

) levels.

Pull a smoke sample from the 

fl

 ue.

The sample should be clean (zero smoke level).

Check the CO

2

 (O

2

) level:

CO

should be at 11 to 12% (O

2

 at 5.9 to 4.5%).

If the CO

2

 is less than 11% (O

2

 more than 5.9%), 

decrease the air and check the smoke level.

Operate the burner from 

low 

fi

 re

 to 

high 

fi

 re

 and 

back to verify operation.
Turn the burner off. Wait one or two minutes (for 
chamber to clear) and then turn on again to verify 
starting characteristics.
Perform limit circuit performance test speci

fi

 ed 

by appliance manufacturer to verify operation of 
burner/appliance combination.

5.

6.

a.

b.

c.

7.

8.

9.

1.

a.

2.

a.

b.

c.

3.

4.

5.

Operating the Burner

Move the 

low-

fi

 re hold

 switch to the 

low 

fi

 re hold

 

position (to hold burner in low 

fi

 re when started).

Verify that the air adjusting cam (

Figure 17

, item 

d

) has been set to the initial low-

fi

 re air setting as 

described under the ‘

Initial Air Settings’

 section.

Open the oil shutoff valves in the oil supply line to 
the burner.
Set the thermostat (or operating control) to call for 
heat.
Close the line switch to the burner. The burner 
motor should start immediately.
If the burner motor does not start, reset the motor 
overload switch (if so equipped) and press the reset 
switch of the burner primary control.
Vent the fuel unit as soon as the burner motor starts 
rotating. (For GeniSys 7505 control refer to the 
control manual for 

Priming the Pump 

procedure.)

To vent:

Attach a clear plastic tube to the air bleed valve 
(

Figure 9 or 10

 as applies, item p

).

Place the end of the tube in a container to catch 
the oil. Then loosen the fuel unit air vent valve.
Tighten the air vent valve after all air has been 
purged.

IF burner stops during venting 

The burner primary control will lockout if 

fl

 ame is not established within its time limit.

This is typically 15 seconds for R7184B 
primary controls, but may be less for other 

fl

 ame supervisory controls.

The burner may lockout several times during 
the period needed to purge all the air. To 
extend air venting time, press the red reset 
button for 1/2 second during the prepurge 
cycle to continue purging.

 IF burner stops after 

fl

 ame is established 

Additional venting is probably required. 
Repeat the air venting procedure.

Once 

fl

 ame is steady, proceed to ‘

Set High-

fi

 re Air’

.

Set High-

fi

 re Air

Allow the burner to run at 

low 

fi

 re

 until the 

appliance has warmed suf

fi

 ciently.

Visually check the 

fl

 ame. The 

fl

 ame should not be 

dark orange or smoky. If the 

fl

 ame appears to be 

smoking, increase the amount of air by readjusting 
the damper indicator to a higher number.
Once the appliance has warmed, the 

high-

fi

 re

 

setting can be checked and adjusted.
Locate the approximate air adjusting plate setting 
for 

high 

fi

 re

 in 

Table 4a

 or 

4b

.

1.

2.

3.

4.

5.

6.

7.

-

-

-

8.

1.

2.

3.

4.

Section: Start the Burner

Содержание CF1400

Страница 1: ...tion start up or service work Save this manual for future reference y y y Incorrect installation adjustment or misuse of this burner could result in death severe personal injury or substantial propert...

Страница 2: ...which your burner ap pliance is installed Make sure Air ventilation openings are clean and unob structed Nothing is blocking burner inlet air openings No combustible materials are stored near the heat...

Страница 3: ...e read all instructions before proceeding Follow all instructions completely This equipment must be installed adjusted and started by a qualified service agency that is licensed and experienced with a...

Страница 4: ...ed in an isolated room provided with outside combustion air Clearances With the burner installed in the appliance there must be adequate space in front of and on the sides of the burner to allow acces...

Страница 5: ...he appliance dimensions are smaller than recommended reduce the firing rate accordingly Table 1 Nozzle Capacities Rated gph 100 psig Pressure Pounds per square inch 125 140 150 175 200 250 275 300 3 0...

Страница 6: ...ing rate required On the CF2300 there are two tube arrangements available Tube A 7 0 to 19 9 GPH per Figure 3 Tube B 10 0 to 19 9 GPH per Figure 3 The CF2300 maximum firing capacity depends on the fir...

Страница 7: ...loss of burner operation resulting in no heat an unplanned process interruption work stoppage and the potential for frozen plumbing or other cold weather property damage Protect Against Dust and Mois...

Страница 8: ...he end of the nozzle line leaving the nut loosely placed so the plates can be moved Connect the high voltage leads from the ignition transformer to the electrodes Check and adjust if necessary the cri...

Страница 9: ...s than dimension D in Figure 8 Thread the pipe into the flange Secure the burner to the appliance by tightening the nuts on the burner flange mounting studs 1 2 3 4 5 6 Figure 7 Adjusting Plate Assy F...

Страница 10: ...ump k Return line to oil tank m One pipe by pass loop 3 8 p Air bleed valve Figure 9 One pipe Oil Flow with B Pump SK9940 Figure 10 Two pipe Oil Flow with B Pump SK9939 Use continuous lengths of heavy...

Страница 11: ...s energized A flame should be established within the factory set trial for ignition time lockout time Lockout The control has shut down for one of the following safety reasons The trial for ignition l...

Страница 12: ...equence The control will continue to Recycle each time the flame is lost until it reaches a pre set time allotment The control will then go into Hard Lockout instead of recycle This feature prevents e...

Страница 13: ...13 CF1400 CF2300 Burner Manual Figure 13 Typical Wiring 7505P Section Wire the Burner...

Страница 14: ...de The burner starts at Low goes to High after the flame stabilization 1 2 3 4 5 6 a period Flame is extinguished when the load is satisfied or a limit opens and the burner is sent to Motor Off Delay...

Страница 15: ...tart up Professional Installation and Service Required Incorrect installation and mishandling of start up could lead to equipment malfunction and result in asphyxiation explosion or fire This burner m...

Страница 16: ...0 6 17 0 60 16 0 7 18 0 70 17 0 8 19 0 80 18 0 9 20 0 90 19 0 100 20 0 B 0 12 5 0 1 13 0 10 10 0 2 14 0 20 13 0 3 15 0 30 14 0 4 16 0 40 15 0 5 17 0 50 16 0 6 18 0 60 17 0 7 18 5 70 18 0 8 19 0 80 18...

Страница 17: ...to its low fire setting This initial setting should be adequate for starting the burner at low fire Once the burner is in operation the air setting will be adjusted for best performance as discussed l...

Страница 18: ...stment Vapor Filled Appliance Allow the unit to cool off and all vapors to dissipate before attempting another start Oil Flooded Appliance Shut off the electrical power and the oil supply to the burne...

Страница 19: ...Burner Move the low fire hold switch to the low fire hold position to hold burner in low fire when started Verify that the air adjusting cam Figure 17 item d has been set to the initial low fire air...

Страница 20: ...3 12 44 DIA 51498 13 92 DIA 51630 16 00 DIA Flange A Flange B Flange C Check the pump pressure and cutoff function Check primary control safety lockout timing Check ignition system for proper operatio...

Страница 21: ...21 CF1400 CF2300 Burner Manual SK9930 3 2 4 5 6 1 SK9931 8 9 7 Section Replacement Parts Figure 19a Burner Replacement Parts...

Страница 22: ...5994U 5201301U 51204U 5201302U 14 Sight glass All models 31346 31346 15 Head assembly 5978 51203 16 Electrode assembly All models 51212 51212 17 Ignition leads 8 1 4 long 11 3 4 long 15 1 4 long 19 1...

Страница 23: ...23 CF1400 CF2300 Burner Manual Figure 19b Burner Replacement Parts Continued SK9936 SK9932 SK9930 14 13 12 10 20 11 21 22 23 15 16 17 18 19...

Страница 24: ...copy of warranty form 61545 please choose one of the following options Visit our website at www beckettcorp com warranty Email your request to rwb customer service beckettcorp com Write to R W Beckett...

Отзывы: