Replace the oil supply line 

fi

 lter. The line 

fi

 lter 

cartridge must be replaced to avoid contamination 
of the fuel unit and nozzle.

Inspect the oil supply system. All 

fi

 ttings should be 

leak-tight. The supply lines should be free of water, 
sludge, and other restrictions.

Remove and clean the pump strainer if applicable.

Replace both nozzles with the speci

fi

 ed brand, 

pattern, gph, 

fl

 ow rate, and spray angle speci

fi

 ed by 

the appliance manufacturer.

Clean and inspect the electrodes for damage, 
replacing any that are cracked or chipped.

Check electrode tip settings. Replace electrodes if 
tips are rounded.

Inspect the igniter spring contacts.

Clean the cad cell lens or other sensor surface, if 
necessary.

Inspect all gaskets. Replace any that are damaged 
or would fail to seal adequately.



Perform Regular Maintenance

Inspect the combustion head and air tube. Remove 
any carbon or foreign matter. Replace all damaged 
units with exact parts.

Clean the blower wheel, air inlet, air guide, burner 
housing, and static plate of any lint or foreign 
material.

If motor is not permanently lubricated, oil motor with 
a few drops of SAE 20 nondetergent oil at each oil 
hole. DO NOT over oil motor. Excessive oiling can 
cause motor failure.

Check motor current. The amp draw should not 
exceed the nameplate rating.

Check all wiring for secure connections or insulation 
breaks.

Check the pump pressure and cutoff function.

Check primary control safety lockout timing.

Check ignition system for proper operation.

Inspect the vent system and chimney for soot 
accumulation or other restriction.

Clean all 

fl

 ue passages and 

fl

 ue pipe. Replace 

corroded or damaged pipes.

Clean the appliance thoroughly according to the 
manufacturer’s recommendations.

Check the burner performance. Refer to the section 

‘Set High-

fi

 re Air’

.

It is good practice to make a record of the service 
performed and the combustion test results.

Monthly Maintenance

 — by owner

Observe combustion air openings and vent system 
for integrity. Openings must be clean and free of 
obstructions.

Check oil lines and 

fi

 ttings to verify there are no 

leaks.

Observe burner ignition and performance to verify 
smooth operation.

Shut the system down if you observe abnormal 
or questionable operation. Call a quali

fi

 ed service 

agency for professional inspection and service.




Section: Perform Regular Maintenance

Annual Professional 
Service Required

Tampering with or making incorrect 

adjustments could lead to equipment 

malfunction and result in asphyxiation, 

explosion or 

fi

 re.

Do not tamper with the burner or controls or make 
any adjustments unless you are a trained and 
quali

fi

 ed service technician.

To ensure continued reliable operation, a quali

fi

 ed 

service technician must service this burner annually.
More frequent service intervals may be required in 
dusty or adverse environments.
Operation and adjustment of the burner requires 
technical training and skillful use of combustion test 
instruments and other test equipment.

y

y

y

y

Содержание CF 2500

Страница 1: ...ation start up or service work Save this manual for future reference y y y Incorrect installation adjustment or misuse of this burner could result in death severe personal injury or substantial property damage To the Professional Qualified Installer or Service Agency Please read and carefully follow all instructions provided in this manual before installing starting or servicing this burner or hea...

Страница 2: ...ractices in the U S refer to the latest edition of NFPA 31 CSA B139 and CSA B140 in Canada Impaired Burner Performance Fire Hazard Do NOT operate the burner beyond specifications outlined in the Table on Page 3 For applications beyond these limits consult Beckett Technical Services at 1 800 645 2876 NOTE Some packaged appliances with burners may be agency listed as a unit to operate beyond these l...

Страница 3: ...nings in the room y y y y y Frozen Plumbing and Water Damage Hazard If the facility is unattended in severely cold weather burner primary control safety lockout heating system component failures power outages or other electrical system failures could result in frozen plumbing and water damage in a matter of hours For protection take preventive actions such as having a security system installed tha...

Страница 4: ...ess whether one pipe with by pass loop or two pipe See Figure 9 for installation of the by pass loop required for one pipe fuel supply installations See Figure 10 for connections to the fuel unit for two pipe fuel supply installations When fuel supply is below the burner fuel unit Use a two pipe oil system when the fuel unit must lift the oil more than 8 feet The return line provided by the two pi...

Страница 5: ... corresponding nozzle from column 1 Rated gph 100 psig two nozzles will be required Example a 5 00 gph nozzle at 300 psig 8 66 gph Verify Firing Rate Refer to appliance manufacturer s instructions if available for firing rate and nozzle selection Otherwise the maximum recommended firing rate for the burner depends on the length of the firing chamber and the distance from the burner center to the c...

Страница 6: ...ure in Inches Water Column W C Maximum Firing Rate U S GPH KP 24 25 Figure 3b Firebox Pressure CF3500 with no Reserve Air 0 2 0 4 0 6 0 8 1 0 0 0 25 20 Firebox Pressure in Inches Water Column W C Maximum Firing Rate U S GPH KR KM 30 35 Install burner with 2 pitch as shown 2 H L T D E 1 4 1 8 Verify Air Tube The information in this section may be disregarded if the air tube is supplied by the appli...

Страница 7: ...sion G is 1 4 nominal Pitch the air tube at 2 from horizontal as shown and secure the flange to the air tube Figure 4 Mount Flange s on Air Tube Stray Light Protect Against Stray Light Lockout Failure to follow these instructions could cause loss of burner operation resulting in no heat an unplanned process interruption work stoppage and the potential for frozen plumbing or other cold weather prop...

Страница 8: ... and 7 Assemble the adjusting plate assembly per the instructions in the assembly packet Slide the secondary adjusting plate item f completely to the left on the indicator adjusting plate item e Finger tighten acorn nut item c to secure the two plates together Slide both plates completely to the left on the primary adjusting plate item g and finger tighten acorn nut item d Slide the completed adju...

Страница 9: ...ng Plate Assembly Legend Figures 6 7 a Adjusting plate assembly b Spline nut for securing nozzle line c Bottom acorn nut d Top acorn nut for setting dim Z only e Indicator adjusting plate f Secondary adjusting plate g Primary adjusting plate Figure 8 Burner Installed in Appliance Front Legend Description Inches H Housing total length 20 J Center to bottom of housing 14 1 2 K Overall housing height...

Страница 10: ... unit nozzle port pressure is factory set at 300 psig At high fire full pressure 300 psig is applied at both oil nozzles causing full input At low fire full pressure 300 psig is applied at one nozzle causing reduced input One pipe Oil System By pass Loop Refer to Figure 9 item k Note the addition of a field installed by pass loop use 3 8 copper tubing from the fuel unit Return port to the Inlet po...

Страница 11: ... port Nozzle Pressure The fuel unit nozzle port pressure is factory set at 300 psig Some original equipment manufacturer burner applications may call for a lower pressure to obtain a required firing rate Do not change this pressure unless directed to do so by the appliance manufacturer 200 psig to 300 psig 200 psig to 300 psig 200 psig to 300 psig 200 psig to 300 psig Section Connect Fuel Lines ...

Страница 12: ...n sent to Motor off Delay Recycle If the flame is lost while the burner is firing the control shuts down the burner enters a 60 second recycle delay and repeats the ignition sequence The control will continue to Recycle each time the flame is lost until it reaches a pre set time allotment The control will then go into Hard Lockout instead of recycle This feature prevents excessive accumulation of ...

Страница 13: ...g and diagnostics Alarm Module For adding isolated low voltage alarm contacts to the base control See Alarm Module Instructions for specifications Contractor s Tool Hand held device for programming and diagnostics Cad Cell Connections Wiring Connections Communication Port 2 Reset Button with Red Light Communication Port 1 Thermostat Terminals Green Light Yellow Light Optional Components Figure 11 ...

Страница 14: ...14 Figure 13 Typical Wiring 7505P Section Wire the Burner ...

Страница 15: ...urner must see flame within 10 seconds if jumper 1 is intact or 4 seconds if jumper 1 is clipped If the flame is not established the burner will lockout if jumper 2 is clipped or recycle if the jumper is intact The burner will then proceed to main flame establishing If flame is not sensed within 3 seconds the burner will lockout or recycle depending on the status of jumper 2 Run With a flame estab...

Страница 16: ...stallation If any of these items are not clear or are unavailable call Beckett at 1 800 645 2876 for assistance y y y y y Do Not Bypass Safety Controls Tampering with or bypassing safety controls could lead to equipment malfunction and result in asphyxiation explosion or fire Safety controls are designed and installed to provide protection Do not tamper with or bypass any safety control If a safet...

Страница 17: ...ide the secondary adjusting plate item f toward the rear of the burner until the number on the indicator plate corresponds to the initial head setting given in Table 6 for the desired firing rate and burner high fire Figure 16 shows a typical example with a 6 head setting When the head position has been set tighten the bottom acorn nut item c and the spline nut item b Start up Checklist Verify the...

Страница 18: ...ush in pin G move the damper by hand so that notch E is between the low fire setting and high fire setting on scale F then release pin G to re engage the motor When the motor is powered it will go to its low fire setting This initial setting should be adequate for starting the burner at low fire Once the burner is in operation the air setting will be adjusted for best performance as discussed late...

Страница 19: ... Skilled in the adjustment of oil burners using combustion test instruments The installation must strictly comply with all applicable codes authorities having jurisdiction and the latest revision of the National Fire Protection Association Standard for the installation of Oil burning Equipment NFPA 31 or CSA B139 and B140 in Canada Regulation by these authorities take precedence over the general i...

Страница 20: ...soon as the burner motor starts rotating To vent Attach a clear plastic tube to the air bleed valve Figure 9 or 10 as applies item p Place the end of the tube in a container to catch the oil Then loosen the fuel unit air vent valve Tighten the air vent valve after all air has been purged IF burner stops during venting The burner primary control will lockout if flame is not established within its t...

Страница 21: ...tion breaks Check the pump pressure and cutoff function Check primary control safety lockout timing Check ignition system for proper operation Inspect the vent system and chimney for soot accumulation or other restriction Clean all flue passages and flue pipe Replace corroded or damaged pipes Clean the appliance thoroughly according to the manufacturer s recommendations Check the burner performanc...

Страница 22: ...Holes 32439U 32439U 13 Rear Cover Door Assembly w Cast Aluminum Door 5994U 51204U w Stamped Sheet Metal Door 5201301U 5201302U 14 Sight Glass All Models 31346 31346 15 Head Assembly KP KM 51475P 51475P KR 51637P 16 Electrode Assembly All Models 51212 51212 17 Ignition Leads 9 1 4 Long 5990092 5990092 10 1 2 Long 5990104 5990104 12 3 4 Long 5990126 5990126 16 1 4 Long 5990162 5990162 20 1 4 Long 59...

Страница 23: ...ual 9 8 7 Figure 18 Burner Replacement Parts 14 10 11 13 12 20 21 22 23 15 16 17 19 18 6 1 2 3 4 5 Figure 19 Adjustable Mounting Plates Air Tube Model Flange A Flange B KP 51498 51630 KM 51498 51630 KR N A 51631 Flange A Flange B ...

Страница 24: ... copy of warranty form 61545 please choose one of the following options Visit our website at www beckettcorp com warranty Email your request to rwb customer service beckettcorp com Write to R W Beckett Corporation P O Box 1289 Elyria OH 44036 NOTE Beckett is not responsible for any labor cost for removal and replacement of equipment THIS WARRANTY IS LIMITED TO THE PRECISE TERMS SET FORTH ABOVE AND...

Отзывы: