12

Wire the Burner 

Install the burner and all wiring in accordance with the 
National Electrical Code and all applicable local codes or 
requirements.

Wire the burner in compliance with all instructions 
provided by the appliance manufacturer. Verify operation 
of all controls in accordance with the appliance 
manufacturer’s guidelines.

See 

Figure 11a

 (7505P) or 

11b

 (RM7897A) for a typical 

wiring diagram (Diagrams are for reference purposes only). 

Trial For Ignition

: The oil solenoid valve is 

energized.  A 

fl

 ame should be established within the 

factory set trial for ignition time (lockout time).

Lockout

: The control has shut down for one of the 

following safety reasons:

The trial for ignition (lockout) time expired 
without 

fl

 ame being established.

The cad cell detected 

fl

 ame at the end of the 

Valve On Delay state.

  To reset the control from lockout click the button 

1-second.

 NOTE: 

A recurrence of the above failure modes 

or a failed welded relay check could cause the 
control to enter a 

Hard Lockout

 state that must 

be reset only by a quali

fi

 ed service technician. 

  To reset from Hard Lockout, hold the reset button 

for 15 seconds until the yellow light turns on.

Ignition Carryover

: Once 

fl

 ame is established, 

the igniter remains on for 10 additional seconds to 
ensure 

fl

 ame stability.  

Run

: With a 

fl

 ame established and the control 

continuing  to detect a 

fl

 ame, the burner will operate 

in the RUN mode until the load demand is satis

fi

 ed 

or a limit opens.

If terminals RC1 and RC2 are jumpered, the 
burner operates in the Low-High-Off Mode. The 
burner starts at Low, goes to High after the 

fl

 ame 

stabilization period. Flame is extinguished when 
the load is satis

fi

 ed or a limit opens, and the 

burner is sent to Motor-Off Delay. 

If a high/low control has been wired between 
terminals RC1 and RC2 the burner starts at 
Low and is released to go High after the 

fl

 ame 

stabilization period. It can repeatedly cycle 
between low and high as necessary to meet load 
demand until the load is satis

fi

 ed or a limit opens. 

The  burner is then sent to Motor-off Delay. 

Recycle

: If the 

fl

 ame is lost while the burner is 

fi

 ring, the control shuts down the burner, enters a 

60 second recycle delay, and repeats the ignition 
sequence.  The control will continue to Recycle 
each time the 

fl

 ame is lost, until it reaches a pre-set 

time allotment.  The control will then go into Hard 
Lockout instead of recycle.  This feature prevents 
excessive accumulation of oil in the appliance 

fi

 ring 

chamber. 

Motor-Off Delay

: The oil solenoid valve is turned 

off and the control delays turning the motor off 
for the set motor-off delay time before the control 
returns to standby.

Pump Prime: 

The igniter and motor are on with the 

oil solenoid valve energized for 4 minutes.  During 
Pump Prime mode, the cad cell is disregarded, 
allowing the technician to prime the pump without 
having to jumper the cad cell.

 

3.

4.

a.

b.

5.

6.

a.

b.

7.

8.

9.

Typical Burner Sequence of Operation - 
GeniSys 7505

Refer to the appliance manufacturer’s wiring 
diagram for actual speci

fi

 cations. Note: GeniSys 

7505 Control on CF2500A only.

Standby

: The burner is idle, waiting for a call for 

heat. 

Valve-On Delay

: The igniter and motor are on while 

the control delays turning on the oil solenoid valve 
for the programmed time.

1.

2.

Electrical Shock Hazard

Electrical shock can cause severe personal injury or death.

Disconnect electrical power before installing or 
servicing the burner.
Provide ground wiring to the burner, metal control 
enclosures and accessories. (This may also be 
required to aid proper control system operation)
Perform all wiring in compliance with the National 
Electric Code ANSI/NFPA 70 (Canada CSA C22.1).

y

y

y

Incorrect Wiring Will 
Result in Improper Control 

Operation

GeniSys 7505 Control wiring label colors may 
not match the wire colors of the burner or other 
manufacturers’ controls.
The GeniSys Control should be wired according to 
the appliance manufacturer’s instructions.

y

y

Fire or Explosion Hazard

Can cause severe injury, death, or property damage.

The control can malfunction if it gets wet, leading to 
accumulation of oil or explosive oil vapors.
Never install where water can 

fl

 ood, drip or 

condense on the control.
Never use a control that has been wet - replace it.

y

y

y

Section: Wire the Burner

Содержание CF 2500

Страница 1: ...ation start up or service work Save this manual for future reference y y y Incorrect installation adjustment or misuse of this burner could result in death severe personal injury or substantial property damage To the Professional Qualified Installer or Service Agency Please read and carefully follow all instructions provided in this manual before installing starting or servicing this burner or hea...

Страница 2: ...ractices in the U S refer to the latest edition of NFPA 31 CSA B139 and CSA B140 in Canada Impaired Burner Performance Fire Hazard Do NOT operate the burner beyond specifications outlined in the Table on Page 3 For applications beyond these limits consult Beckett Technical Services at 1 800 645 2876 NOTE Some packaged appliances with burners may be agency listed as a unit to operate beyond these l...

Страница 3: ...nings in the room y y y y y Frozen Plumbing and Water Damage Hazard If the facility is unattended in severely cold weather burner primary control safety lockout heating system component failures power outages or other electrical system failures could result in frozen plumbing and water damage in a matter of hours For protection take preventive actions such as having a security system installed tha...

Страница 4: ...ess whether one pipe with by pass loop or two pipe See Figure 9 for installation of the by pass loop required for one pipe fuel supply installations See Figure 10 for connections to the fuel unit for two pipe fuel supply installations When fuel supply is below the burner fuel unit Use a two pipe oil system when the fuel unit must lift the oil more than 8 feet The return line provided by the two pi...

Страница 5: ... corresponding nozzle from column 1 Rated gph 100 psig two nozzles will be required Example a 5 00 gph nozzle at 300 psig 8 66 gph Verify Firing Rate Refer to appliance manufacturer s instructions if available for firing rate and nozzle selection Otherwise the maximum recommended firing rate for the burner depends on the length of the firing chamber and the distance from the burner center to the c...

Страница 6: ...ure in Inches Water Column W C Maximum Firing Rate U S GPH KP 24 25 Figure 3b Firebox Pressure CF3500 with no Reserve Air 0 2 0 4 0 6 0 8 1 0 0 0 25 20 Firebox Pressure in Inches Water Column W C Maximum Firing Rate U S GPH KR KM 30 35 Install burner with 2 pitch as shown 2 H L T D E 1 4 1 8 Verify Air Tube The information in this section may be disregarded if the air tube is supplied by the appli...

Страница 7: ...sion G is 1 4 nominal Pitch the air tube at 2 from horizontal as shown and secure the flange to the air tube Figure 4 Mount Flange s on Air Tube Stray Light Protect Against Stray Light Lockout Failure to follow these instructions could cause loss of burner operation resulting in no heat an unplanned process interruption work stoppage and the potential for frozen plumbing or other cold weather prop...

Страница 8: ... and 7 Assemble the adjusting plate assembly per the instructions in the assembly packet Slide the secondary adjusting plate item f completely to the left on the indicator adjusting plate item e Finger tighten acorn nut item c to secure the two plates together Slide both plates completely to the left on the primary adjusting plate item g and finger tighten acorn nut item d Slide the completed adju...

Страница 9: ...ng Plate Assembly Legend Figures 6 7 a Adjusting plate assembly b Spline nut for securing nozzle line c Bottom acorn nut d Top acorn nut for setting dim Z only e Indicator adjusting plate f Secondary adjusting plate g Primary adjusting plate Figure 8 Burner Installed in Appliance Front Legend Description Inches H Housing total length 20 J Center to bottom of housing 14 1 2 K Overall housing height...

Страница 10: ... unit nozzle port pressure is factory set at 300 psig At high fire full pressure 300 psig is applied at both oil nozzles causing full input At low fire full pressure 300 psig is applied at one nozzle causing reduced input One pipe Oil System By pass Loop Refer to Figure 9 item k Note the addition of a field installed by pass loop use 3 8 copper tubing from the fuel unit Return port to the Inlet po...

Страница 11: ... port Nozzle Pressure The fuel unit nozzle port pressure is factory set at 300 psig Some original equipment manufacturer burner applications may call for a lower pressure to obtain a required firing rate Do not change this pressure unless directed to do so by the appliance manufacturer 200 psig to 300 psig 200 psig to 300 psig 200 psig to 300 psig 200 psig to 300 psig Section Connect Fuel Lines ...

Страница 12: ...n sent to Motor off Delay Recycle If the flame is lost while the burner is firing the control shuts down the burner enters a 60 second recycle delay and repeats the ignition sequence The control will continue to Recycle each time the flame is lost until it reaches a pre set time allotment The control will then go into Hard Lockout instead of recycle This feature prevents excessive accumulation of ...

Страница 13: ...g and diagnostics Alarm Module For adding isolated low voltage alarm contacts to the base control See Alarm Module Instructions for specifications Contractor s Tool Hand held device for programming and diagnostics Cad Cell Connections Wiring Connections Communication Port 2 Reset Button with Red Light Communication Port 1 Thermostat Terminals Green Light Yellow Light Optional Components Figure 11 ...

Страница 14: ...14 Figure 13 Typical Wiring 7505P Section Wire the Burner ...

Страница 15: ...urner must see flame within 10 seconds if jumper 1 is intact or 4 seconds if jumper 1 is clipped If the flame is not established the burner will lockout if jumper 2 is clipped or recycle if the jumper is intact The burner will then proceed to main flame establishing If flame is not sensed within 3 seconds the burner will lockout or recycle depending on the status of jumper 2 Run With a flame estab...

Страница 16: ...stallation If any of these items are not clear or are unavailable call Beckett at 1 800 645 2876 for assistance y y y y y Do Not Bypass Safety Controls Tampering with or bypassing safety controls could lead to equipment malfunction and result in asphyxiation explosion or fire Safety controls are designed and installed to provide protection Do not tamper with or bypass any safety control If a safet...

Страница 17: ...ide the secondary adjusting plate item f toward the rear of the burner until the number on the indicator plate corresponds to the initial head setting given in Table 6 for the desired firing rate and burner high fire Figure 16 shows a typical example with a 6 head setting When the head position has been set tighten the bottom acorn nut item c and the spline nut item b Start up Checklist Verify the...

Страница 18: ...ush in pin G move the damper by hand so that notch E is between the low fire setting and high fire setting on scale F then release pin G to re engage the motor When the motor is powered it will go to its low fire setting This initial setting should be adequate for starting the burner at low fire Once the burner is in operation the air setting will be adjusted for best performance as discussed late...

Страница 19: ... Skilled in the adjustment of oil burners using combustion test instruments The installation must strictly comply with all applicable codes authorities having jurisdiction and the latest revision of the National Fire Protection Association Standard for the installation of Oil burning Equipment NFPA 31 or CSA B139 and B140 in Canada Regulation by these authorities take precedence over the general i...

Страница 20: ...soon as the burner motor starts rotating To vent Attach a clear plastic tube to the air bleed valve Figure 9 or 10 as applies item p Place the end of the tube in a container to catch the oil Then loosen the fuel unit air vent valve Tighten the air vent valve after all air has been purged IF burner stops during venting The burner primary control will lockout if flame is not established within its t...

Страница 21: ...tion breaks Check the pump pressure and cutoff function Check primary control safety lockout timing Check ignition system for proper operation Inspect the vent system and chimney for soot accumulation or other restriction Clean all flue passages and flue pipe Replace corroded or damaged pipes Clean the appliance thoroughly according to the manufacturer s recommendations Check the burner performanc...

Страница 22: ...Holes 32439U 32439U 13 Rear Cover Door Assembly w Cast Aluminum Door 5994U 51204U w Stamped Sheet Metal Door 5201301U 5201302U 14 Sight Glass All Models 31346 31346 15 Head Assembly KP KM 51475P 51475P KR 51637P 16 Electrode Assembly All Models 51212 51212 17 Ignition Leads 9 1 4 Long 5990092 5990092 10 1 2 Long 5990104 5990104 12 3 4 Long 5990126 5990126 16 1 4 Long 5990162 5990162 20 1 4 Long 59...

Страница 23: ...ual 9 8 7 Figure 18 Burner Replacement Parts 14 10 11 13 12 20 21 22 23 15 16 17 19 18 6 1 2 3 4 5 Figure 19 Adjustable Mounting Plates Air Tube Model Flange A Flange B KP 51498 51630 KM 51498 51630 KR N A 51631 Flange A Flange B ...

Страница 24: ... copy of warranty form 61545 please choose one of the following options Visit our website at www beckettcorp com warranty Email your request to rwb customer service beckettcorp com Write to R W Beckett Corporation P O Box 1289 Elyria OH 44036 NOTE Beckett is not responsible for any labor cost for removal and replacement of equipment THIS WARRANTY IS LIMITED TO THE PRECISE TERMS SET FORTH ABOVE AND...

Отзывы: