background image

Содержание AquaSmart 7600WTM

Страница 1: ......

Страница 2: ...AquaSmart Wireless Temperature Module Model 7600WTM It adds outdoor reset capability to the AquaSmart control by overriding the control s built in HeatManager algorithm when installed...

Страница 3: ...Remove power from AquaSmart snap in AWM restore power...

Страница 4: ...Remove the internal cartridge containing the battery cell from the Wireless Temperature Sensor WTS Press in the plastic tabs and pull the cartridge out...

Страница 5: ...Remove the plastic insert on the battery terminal Make sure battery is inserted properly see polarity mark on battery holder...

Страница 6: ...Press the WTS button once The LED should flash five times...

Страница 7: ...lator Menu More Options Economizer On Off Efficiency Setting History Screens Delay Off Time Delay On Time Circulator on TT ZR LWCO Menu Pressure Menu Wireless Menu Using the AquaSmart s display naviga...

Страница 8: ...last transmission was received within the last few minutes If the OAT screen says AS OF 18 12 AGO press the WTS button once If the value does not update there is a problem with the connectivity of the...

Страница 9: ...te to screen 2 The signal strength screen indicates the strength of the connection between the AWM and WTS At least 3 darkened bars are recommended for operation with 6 or more indicating a good conne...

Страница 10: ...Navigate to Screen 3 If the screen says REPLACE the battery needs replaced...

Страница 11: ...Navigate to Screen 4 Pressing ENTER RESET on this screen will toggle the setting on and off ON default indicates that the outdoor reset algorithm will override the HeatManagerTM algorithm...

Страница 12: ...reen 5 Press ENTER RESET on this screen and follow the on screen instructions to change this setting This number specifies the outdoor temperature at which the boiler reset temperature will be at its...

Страница 13: ...o Screen 6 Press ENTER RESET on this screen and follow the on screen instructions to change this setting This number specifies the outdoor temperature at which the boiler high limit will be at its max...

Страница 14: ...ll toggle the setting on and off ON will turn the low limit of the AquaSmart off when the outdoor temperature is above 70 F 21 C Turning this feature on can help to increase fuel savings OFF default w...

Страница 15: ...reen and follow the on screen instructions to change this setting This is the OTR s equivalent of the HeatManager s 20 minute kickout function Every 10 consecutive minutes of CFH or burner on time the...

Отзывы: