background image

11

DE

GB

FR

NL

Caution
During all wiring work, the system must be disconnected from the power by removing the CEE plug or 

switching off the main switch. Observe the applicable EN guidelines during installation.

3. Motor/control connection

The drive cable (12-wire) must be connected to the appropriate terminals in accordance with the connection plan (not re-
quired if connection has already been carried out by Becker). The terminal designations correspond to the numbers of the 
drive cable wires.
The fitted CEE plug can be used as the main switch. If the control is connected without the CEE plug (e.g. permanent con-
nection), a main switch must be connected into the mains feed, which disconnects all the poles according to the overvoltage 
category III.
Separate connection cables are required for outdoor use, and for PVC connections these cables have to be laid in a protec-
tive tube. 

Control

Checking the running direction

Insert the CEE plug into the CEE socket or switch on the main switch. Now use the UP and DOWN buttons to check whether 
the running direction of the door agrees with these commands.

If the running direction does not correspond to the arrow direction:

Remove the CEE plug, or switch the main switch off. Swap the L1 and L3 connections, for example, at the mains connection 
terminals (see connection plan). Resume installation.

Setting the end limits

The control is set at the factory so that ascent is carried out in self¬locking mode and descent in deadman’s mode. To facilitate 
moving to the final position when setting the limit switches, you can switch the ascent from self¬locking to deadman’s mode 
with the DIP switch no.1. 

Lower end limit setting 

Move the door to the bottom end limit with the DOWN button (deadman’s mode). Approach the desired end limit for the door 
by “tapping” if necessary. Set the limit switch cam for DOWN (black) according to the operating instructions for the direct 
mount drive used.

Upper end limit setting

Move the door to the top end limit with the UP button (deadman’s mode). Once again, approach the desired top end limit of 
the door by “tapping” if necessary. Set the limit switch cam for UP (grey) according to the operating instructions for the direct 
mount drive used.

Setting the safety limit switches

The safety limit switches (yellow) are set with approx. 3° delay to the respective operating limit switch. Observe the relevant 
information in the operating instructions for the direct mount drive. If a safety limit switch is contacted, the control voltage is 
switched off. The relevant control cam must then be turned away manually from the limit switching micro switch, or cleared 
by manual activation (e.g. crank).

Setting the function switch S7

With function switch S7 (orange) it is possible to control the relay REL1. A potential-free changeover contact is available via the 
output terminals.  For example, this enables the the connection of simple traffic light function or a door status display.

Setting of the function switch S8

With function switch S8 (green) it is possible to set a partial opening position of the door which can be activated or deactivated 
via an external selector switch.

Note
On principle, the precise adjustment of the limit positions is carried out with the fine adjustment screw of 

the respective control cam (please see also the operating instructions for the door drive).

Commissioning of the system

Содержание S10AF

Страница 1: ...s Users Please forward accordingly These instructions must be kept for future reference Notice de montage et d utilisation Commande de porte Informations importantes pour l installateur l électricien l utilisateur À transmettre à la personne concernée Cette notice doit être conservée par l utilisateur Montage en gebruiksaanwijzing Deurbesturing Informations importantes pour l installateur l électr...

Страница 2: ...ng 4 Inbetriebnahme 5 Funktionsbeschreibung 6 Was tun wenn 7 Stromlaufplan 7 Anschlussplan 8 Technische Daten 8 General 10 Warranty 10 Intended use 10 Safety information 10 Installation instructions 10 Commissioning of the system 11 Functional description 12 What should you do if 13 Wiring diagram 13 Connection plan 14 Technical data 14 ...

Страница 3: ...6 Mise en service 17 Descriptif fonctionnel 18 Que faire si 19 Schéma de câblage 19 Plan des connexions 20 Caractéristiques techniques 20 Algemeen 22 Garantie 22 Doelmatig gebruik 22 Veiligheidsvoorschriften 22 Montage 22 Inbedrijfstelling 23 Functiebeschrijving 24 Wat te doen indien 25 Schakelschema 25 Aansluitschema 26 Technische gegevens 26 ...

Страница 4: ...mäßem Han deln haftet Becker Antriebe nicht für dadurch verursachte Schäden Lesen sie diese Anleitung vor den Arbeiten sorgfältig durch Die Arbeiten an den elektrischen Einrichtungen sind nur von einer qualifizierten Elektrofachkraft auszuführen Halten Sie die gesetzlichen Vorschriften Sicherheit Unfallverhütung insbesondere die Bestimmungen der Berufsgenos senschaft BGR 232 bzw EN 12453 Nutzungss...

Страница 5: ...ung heranzutasten kann mit dem Schalter DIP1 die AUF Richtung von Selbsthaltung in Totmann umgeschaltet werden Einstellung untere Endlage Mit der Taste AB fahren Sie das Tor in die untere Endlage Totmann Betrieb Nähern Sie sich ggf durch Tippen an die gewünschte Endlage des Tores Stellen Sie den Endschalternocken für AB schwarz gemäß der Betriebsanleitung des ver wendeten Aufsteckantriebs ein Eins...

Страница 6: ...rst die Stop Taste gedrückt werden STOP Das sich öffnende oder schließende Tor kann durch Drücken der STOP Taste Frontseite in jeder Lage sofort angehalten werden Tor AB Durch Drücken der AB Taste Frontseite schließt das Tor im Totmann Betrieb Bei Erreichen der unteren Endlage stoppt das Tor automatisch Steuereingänge und externe Befehlsgeber Externe Befehlsgeber AUF STOP AB Es kann ein zusätzlich...

Страница 7: ... Taster Schlaffseilendschalter Sicherheitsendschal ter überprüfen Anschlussadern auf festen Sitz in den Klemmen prüfen Geräteinterne Feinsicherung prüfen Falls defekt austauschen Bei erneutem Ausfall benachrichtigen Sie Ihren Fachhändler Keine Reaktion auf Tastendruck Eingangsklemmen für externe STOP Taste brücken Steckverbindung der Dreifachdrucktaster überprüfen Das Tor öffnet nur im Totmann Bet...

Страница 8: ...g Anschlussplan Technische Daten Typ S10AF Netzanschluß 3 x 400 230V 50 60 Hz L1 L2 L3 N PE Max Motornennleistung 2 8 KW Gewicht 1 5 kg Abmessungen 182 x 180 x 90 B x H x T Schutzart IP 54 IP 65 optional nur für Montage im Innenraum ...

Страница 9: ...9 DE GB FR NL ...

Страница 10: ...ications are not permitted in order to protect the safety of the users and others since these actions can impair the system s safety resulting in personal injuries and property damage Becker Antriebe shall not accept liability for damages arising from such actions Always observe the information in these instructions when operating or repairing the system Becker Antriebe shall not accept liability ...

Страница 11: ...from self locking to deadman s mode with the DIP switch no 1 Lower end limit setting Move the door to the bottom end limit with the DOWN button deadman s mode Approach the desired end limit for the door by tapping if necessary Set the limit switch cam for DOWN black according to the operating instructions for the direct mount drive used Upper end limit setting Move the door to the top end limit wi...

Страница 12: ...oor is descending you must press the Stop button first of all STOP The opening or closing door can be stopped immediately in any position by pressing the STOP button front Door DOWN Pressing the DOWN button front closes the door in deadman s mode The door stops automatically when the lower end limit is reached Control inputs and external pick ups External pick ups UP STOP DOWN An additional triple...

Страница 13: ...rcuit e g emergency stop switch slack cable limit switch safety limit switch Check that connection wires are securely fixed in the terminals Check fine wire fuse inside the unit Replace if defective If failure occurs again inform your dealer No response when buttons are pressed Bridge the input terminals for the external STOP button Check plug in connections of triple pushbuttons The door only ope...

Страница 14: ...ns Connection plan Technical data Type S10 AF Power supply 3 x 400 230V 50 60 Hz L1 L2 L3 N PE Max rated power of motor 2 8 KW Weight 1 5 kg Dimensions 182 x 180 x 90 W x H x D Class of protection IP 54 IP 65 optional for indoor use only ...

Страница 15: ...15 DE GB FR NL ...

Страница 16: ...fications ne sont pas autorisées pour des raisons de sécurité dans le but de protéger l utilisateur et les tiers car elles pourraient entraver la sécurité de l installation et ainsi présenter un risque de domma ges corporels et matériels BECKER Antriebe GmbH décline toute responsabilité pour les dommages dus au non respect de cette consigne Les indications de cette notice d utilisation doivent êtr...

Страница 17: ...e au mode homme mort Réglage de la position finale basse Déplacez la porte en position finale basse au moyen de la touche DESCENTE mode Homme mort Approchez vous de la position finale souhaitée le cas échéant en mode pas à pas Réglez la came du fin de course pour la DESCENTE noir conformément aux instructions de service du motoréducteur à arbre creux utilisé Réglage de la position finale haute Dép...

Страница 18: ...RRÊT ARRÊT La porte en cours d ouverture ou de fermeture peut être immédiatement stoppée dans n importe quelle position en ac tionnant la touche ARRÊT face avant DESCENTE de la porte En actionnant la touche DESCENTE face avant la porte se ferme en mode Homme mort Lorsque la position finale basse est atteinte la porte stoppe automatiquement Entrées de commande et contrôles externes Poussoirs extern...

Страница 19: ...ateur actionné par câble détendu commutateur de sécurité Vérifier que les fils de connexion sont bien raccordés aux bornes Vérifier les fusibles pour courant faible internes à l appareil En cas de défectuosité les remplacer En cas de nouveau dysfonctionnement informez votre revendeur spé cialisé Pas de réaction à l actionnement de touches Ponter les bornes d entrées pour la touche STOP externe Vér...

Страница 20: ...éristiques techniques Type S10AF Alimentation secteur 3 x 400 230V 50 60 Hz L1 L2 L3 N PE Puissance nominale maxi du moteur 2 8 KW Poids 1 5 kg Dimensions 182 x 180 x 90 l x H x P Indice de protection IP 54 IP 65 en option exclusivement pour un montage à l intérieur ...

Страница 21: ...21 DE GB FR NL ...

Страница 22: ...uk kunnen doen aan de veiligheid van de installatie en er daardoor gevaar bestaat voor personen en goederen Voor schade die in deze gevallen ontstaat aanvaardt Becker Antriebe GmbH geen aansprake lijkheid Neem bij het gebruik van de installatie of bij onderhoud de aanwijzingen in deze handleiding in acht Bij ondeskundig handelen aanvaardt Becker Antriebe GmbH geen aansprakelijkheid voor daardoor v...

Страница 23: ...nnen vinden kan met de functieschakelaar DIP 1 de OMHOOG richting van zelfvergrendeling naar dodeman worden omgeschakeld Instelling van de onderste eindpositie Met de toets OMLAAG brengt u de deur in de onderste eindpositie dodemanbedrijf Benader eventueel door tippen de gewenste eindpositie van de deur Stel de eindschakelaarnok voor OMLAAG zwart in overeenkomstig de handleiding van de gebruikte o...

Страница 24: ...ng moet worden omgezet dan moet eerst de stoptoets worden ingedrukt STOP De openende of sluitende deur kan door het indrukken van de STOP toets voorzijde in iedere positie onmiddellijk worden gestopt Deur OMLAAG Door op de OMLAAG toets voorzijde te drukken sluit de deur in dodemanbedrijf Bij het bereiken van de onderste eind positie stopt de deur automatisch Besturingsingangen en externe contactge...

Страница 25: ...chakelaar slappekabeleindschakelaar veiligheids eindschakelaar controleren Aansluitaders controleren op vaste zitting in de klemmen Inwendige zekering controleren Indien defect vervangen Bij herhaald defect uw gespecialiseerde handelaar raadplegen Geen reactie bij indrukken van een toets Ingangsklemmen voor externe STOP toets overbruggen Insteekverbinding van de drievoudige druktoets controleren D...

Страница 26: ...schema Technische gegevens Type S10AF Netaansluiting 3 x 400 230V 50 60 Hz L1 L2 L3 N PE Max nominaal motorvermogen 2 8 KW Gewicht 1 5 kg Afmetingen 182 x 180 x 90 B x H x T Isolatieklasse IP 54 IP 65 optioneel alleen voor montage binnenshuis ...

Страница 27: ...27 DE GB FR NL ...

Страница 28: ...4023 630 205 0b 02 08 Becker Antriebe GmbH 35764 Sinn Germany www becker antriebe com ...

Отзывы: