Local operation with a single button
Connection
Only use a single button (normally open). Only connect one drive for each push-button.
The length of cable between the tubular drive and the push-button must not exceed 20 m.
The push-button must not be operated during the first five seconds after the mains voltage
has been switched on.
N
L
PE
Button (normally open)
black
brown
blue
green/yellow
Button commands
< 1 second
Moves in maintained operation
> 1 second
Moves in dead-man mode
Double-tap < 1 second
Moves to the intermediate position (in alternation if both are programmed)
Operation proceeds in this sequence: "Travel-Stop-Travel-in-the-opposite-direction-Stop".
17 - en