![Beck com.tom M-BUS 6.1S Скачать руководство пользователя страница 1](http://html1.mh-extra.com/html/beck/com-tom-m-bus-6-1s/com-tom-m-bus-6-1s_startup-manual_2718178001.webp)
com
.
tom
M-BUS 6.1S – Start-up Guide
In widely distributed systems or in environ-
ments without network infrastructure wire-
less solutions are required for the simplest
telecontrol/remote maintenance functions.
With the integrated switch and the auxiliary
functions com.tom a compact VPN and
NAT cheap local network structure to ac-
cess controls and devices is given.
The communication mechanism of the
com.tom devices ensures problem-free use
in all wireless networks without the need for
special SIM cards.
Device may only be put into service and operated by qualified
personnel.
The device is designed for an installation on a ground-
ed 35 mm DIN rail in dry rooms.
Insert the SIM card in the device’s rear before the installation on the
DIN rail. The device must be switched off.
Never use the device in areas where the operation of wireless
equipment is prohibited.
The location for the antenna must guarantee the recommended
radiological limits (be at least 20 cm from persons and other anten-
nas).
When the antenna is installed outdoors the lightning protection
standard VDE V0185 must be complied with. The EMC lightning
protection zone concept must be observed. The device must be
switched off during work on the antenna.
It cannot be guaranteed, that there will not be any harmful interfer-
ence for other devices. In case of interferences install the device or
the antenna in another location.
After the installation the housing of the device is connected with
functional earth.
The power supply must be a grounded circuit (PELV). The power
supply must be a limited power source according to EN60950-1
Cap. 2.5 or the device must be provided with an anti-surge fuse of
2A. The digital I/Os are provided with a detached anti-surge fuse of
4A.
Pin Assignment
Power Supply
FE
Functional earth
GND Ground
VCC
24 VDC
Digital I/Os
+
24 VDC
S01,S02
Digital pulse input, source
Out1, Out2
Digital output, source
MB+, MB-
M-Bus
-
Ground
Serial Interface
RS232
RS485
RS422
Pin 1
NC
A(-/Y)
A(TxD)
Pin 2
RxD
NC
NC
Pin
3 TxD NC NC
Pin 4
NC
NC
A'(RxD)
Pin 5
GND
GND
GND
Pin 6
NC
B(+/Z)
B(TxD)
Pin 7
RTS
NC
NC
Pin 8
CTS
NC
NC
Pin 9
NC
NC
B'(RxD)
Housing
Connected to functional earth
Ethernet Interfaces
Green LED
Link indication
Yellow LED
Activity indication
LEDs
Modem
Modem is initialized
GSM/GPRS
GPRS Internet Connection successful
Status A
Communication with Portal successful
Status B
Diagram loaded (on) / executed (flashing)
Power
Device is powered
Other Interfaces
SD card interface
MMC/SD card
Antenna connector
SMA connector
SIM card interface
SIM card
Getting Started
Wire the com.tom device according to the technical data.
Afterwards get the Getting Started documentation WEB-PLC
at http://www.com-tom.de/start and follow the steps described
there to put your com.tom device into operation. When using
the GPJ Power Supply Connector (labeled in white), only
com.tom GRAPHIC may be connected to Port ETH1.3/GPJ.
General Data
Size (W x L x H)
65 x 103 x 62 mm
Operating temperature
0 bis 55 °C
Electrical shock
Class III
Protection rating
IP20
EMC emission
IEC 61000-6-4
EMC immunity
IEC 61000-6-2
Compliance
CE, RoHS
Electrical Data
Supply voltage
24 VDC (
±
15 %)
Active current
< 0.12 A (without I/Os)
≤
0.5 A / output
≤
0.5 A / GPJ
Scope of supply
1 Piece
com.tom M-BUS 6.1S
1 Piece
Start-up guide
2 Piece
Connector 3-pin
1 Piece
Connector 10-pin
1 Piece
Label MAC-ID
Copyright © 2015 Beck IPC GmbH
http://www.com-tom.de