background image

 

 
 

com

.

tom

 

BASIC 5.2 – Start-up Guide

 

 

The com.tom BASIC device communicate with 
the web portal via Ethernet and the existing 
network infrastructure. The communication 
mechanism has a low data volume and can be 
integrated easily in the existing network infra-
structure. 

 

 

 

 

 

 

Device may only be put into service and operated by qualified 
personnel. 

The device is designed for an installation on a grounded 35 mm 
DIN Rail in dry rooms. 

 

After the installation the housing of the device is connected with 
functional earth. 
The power supply must be a grounded circuit (PELV). 

The power supply must be a limited power source according to 
EN60950-1 cap. 2.5 or the device must be provided with an anti-
surge fuse of 2 A. The digital I/Os are provided with a detached 
anti-surge fuse of 4 A. 

 

Pin Assignment 

Power Supply 
FE 

Functional earth 

GND Ground 
VCC 

24 VDC 

 
 

 
 
 
 

Digital I/Os 

24 VDC 

I0 - I3 

Digital input, sink 

Q0 - Q3 

Digital output, source 

- Ground 

Serial Interface 

 

RS232 

RS485 

RS422 

Pin 1 

NC 

A(-/Y) 

A(TxD) 

Pin 2 

RxD 

NC 

NC 

Pin 

3 TxD NC  NC 

Pin 4 

NC 

NC 

A'(RxD) 

Pin 5 

GND 

GND 

GND 

Pin 6 

NC 

B(+/Z) 

B(TxD) 

Pin 7 

RTS 

NC 

NC 

Pin 8 

CTS 

NC 

NC 

Pin 9 

NC 

NC 

B'(RxD) 

Housing 

Connected to functional earth 

 

 

 

 

Ethernet Interface 
Green LED 

Link indication 

Yellow LED 

Activity indication 

LEDs 
Status A 

Freely programmable 

Status B 

Freely programmable 

Status C 

Communication with Portal successful 

Status D 

Program loaded (on) / executed (flashing) / 
stopped (off) 

Power 

Device is powered 

Other Interfaces 
SD card interface 

MMC/SD memory cards 

SIM card interface 

no function 

Getting Started 

Wire the com.tom device according to the technical data. Get the 
Getting Started documentation com.tom-CODESYS at www.beck-
ipc.com/gettingstarted and follow the steps described there to put 
your com.tom device into operation. 

General Data 

Size (W x L x H) 

46 x 103 x 63 mm 

Operating temperature 

0 to 55 °C  

Electrical shock 

Class III 

Protection rating 

IP20 

EMC emission 

IEC 61000-6-4 

EMC immunity 

IEC 61000-6-2 

Compliance 

CE, RoHS 

Electrical Data 

Supply voltage 

24 VDC (

15 %) 

Active current 

< 80 mA (without I/Os) 

 0.5 A / output 

 

Scope of supply 

 
1 Piece 

com.tom BASIC 5.2 

1 Piece 

Start-up guide 

1 Piece 

Connector 3-pin 

1 Piece 

Connector 10-pin 

 
 

 

Copyright © 2013 Beck IPC GmbH

www.beck-ipc.com

Отзывы: