BASIC 5.2 – Start-up Guide
The com.tom BASIC device communicate with
the web portal via Ethernet and the existing
network infrastructure. The communication
mechanism has a low data volume and can be
integrated easily in the existing network infra-
structure.
Device may only be put into service and operated by qualified
personnel.
The device is designed for an installation on a grounded 35 mm
DIN Rail in dry rooms.
After the installation the housing of the device is connected with
functional earth.
The power supply must be a grounded circuit (PELV).
The power supply must be a limited power source according to
EN60950-1 cap. 2.5 or the device must be provided with an anti-
surge fuse of 2 A. The digital I/Os are provided with a detached
anti-surge fuse of 4 A.
Pin Assignment
Power Supply
FE
Functional earth
GND Ground
VCC
24 VDC
Digital I/Os
+
24 VDC
I0 - I3
Digital input, sink
Q0 - Q3
Digital output, source
- Ground
Serial Interface
RS232
RS485
RS422
Pin 1
NC
A(-/Y)
A(TxD)
Pin 2
RxD
NC
NC
Pin
3 TxD NC NC
Pin 4
NC
NC
A'(RxD)
Pin 5
GND
GND
GND
Pin 6
NC
B(+/Z)
B(TxD)
Pin 7
RTS
NC
NC
Pin 8
CTS
NC
NC
Pin 9
NC
NC
B'(RxD)
Housing
Connected to functional earth
Ethernet Interface
Green LED
Link indication
Yellow LED
Activity indication
LEDs
Status A
Freely programmable
Status B
Freely programmable
Status C
Communication with Portal successful
Status D
Program loaded (on) / executed (flashing) /
stopped (off)
Power
Device is powered
Other Interfaces
SD card interface
MMC/SD memory cards
SIM card interface
no function
Getting Started
Wire the com.tom device according to the technical data. Get the
Getting Started documentation com.tom-CODESYS at www.beck-
ipc.com/gettingstarted and follow the steps described there to put
your com.tom device into operation.
General Data
Size (W x L x H)
46 x 103 x 63 mm
Operating temperature
0 to 55 °C
Electrical shock
Class III
Protection rating
IP20
EMC emission
IEC 61000-6-4
EMC immunity
IEC 61000-6-2
Compliance
CE, RoHS
Electrical Data
Supply voltage
24 VDC (
15 %)
Active current
< 80 mA (without I/Os)
≤
0.5 A / output
Scope of supply
1 Piece
com.tom BASIC 5.2
1 Piece
Start-up guide
1 Piece
Connector 3-pin
1 Piece
Connector 10-pin
Copyright © 2013 Beck IPC GmbH