Anti-static handling guidelines
Make sure that electrostatic handling precautions are taken immediately before handling PCBs and
other static sensitive components.
Before handling any static-sensitive items, operators should get rid of any electrostatic charge by
touching a sound safety earth. Always handle PCBs by their sides and avoid touching any
components.
1
Installation
1.1
Mounting The Unit
The Phone plate can be removed from the back box by removing the
four screws marked A in the diagram on the right and lifting the bracket up.
The phone can be removed by unclipping the grey connector at the
hook switch end of the cable.
The back box can now be prepared for the cable from the EVC
System, this is a 2 core 1.5mm CSA Enhanced fire rated cable.
Knock out the cable knock out and gland the cable to the top right of
the box, or if you are coming in from the rear drill where shown in
dotted lines below (this is the only place clear of all operational parts
of the outstation) a rubber grommet or gland should be used to protect
the cable
The Back box can now be mounted by
using the holes marked B, the height of
the unit needs to be 1300 to 1400mm from finished floor level to the
centre of the outstation (as shown below)
If flush mounting using the BTAR bezel, the unit wants fitting to a
maxium depth of 95mm for correct opening
of the door.
The bezel is attached to the wall using
clear bathroom sealer.
BTAR Manual