75.0034.03 ULTIMO 20220120 

Page 1 of 20

ULTIMO

EN

ACTIVATION AND SAFETY SENSOR FOR 

AUTOMATIC, SLIDING DOORS

Visit website for 
available languages 
of this document.

Содержание ULTIMO

Страница 1: ...75 0034 03 ULTIMO 20220120 Page 1 of 20 ULTIMO EN ACTIVATION AND SAFETY SENSOR FOR AUTOMATIC SLIDING DOORS Visit website for available languages of this document ...

Страница 2: ...5 0034 03 ULTIMO 20220120 1 cover 2 light pipe 3 radar antenna 4 AIR receiver 5 AIR emitter 6 LCD 7 for internal use only 8 LED 9 AIR curtain angle adjustment knob 10 main adjustment knob 11 main connector 12 for future development DESCRIPTION ...

Страница 3: ... relay potential and polarity free 1 A 30 VDC 0 5 9 seconds Optofet output 2 max contact current max contact voltage hold time solid state relay potential and polarity free 400 mA 42 VAC VDC 0 3 1 second Test Monitoring input sensitivity response time on request low 1 V high 10 V max 30V 5 ms typ Supply voltage 12 24 VAC 10 12 30 VDC 10 Power consumption 3 2 W Temperature range 13 131 F 0 95 relat...

Страница 4: ...orized personnel Following installation always test for proper operation according to ANSI 156 10 before leaving the premises The door control unit and the header cover profile must be correctly grounded SAFETY It is recommended to clean the optical parts at least once a year or more if required due to environmental conditions Do not use aggressive products to clean the optical parts MAINTENANCE R...

Страница 5: ... inches from the bottom of the door header 2 Route the harness 20 5349 using the wire stay as shown MOUNTING DUAL SLIDER SINGLE SLIDER Sensor connectivity power and relays must utilize only the supplied harness Sensor is intended to be monitored for proper operation by the door operator or system Harness shall be routed separated from any Mains or non Class 2 voltage cable for correct operation or...

Страница 6: ...ctional Sensor monitoring functionality is automatic by default Ensure purple wires are properly connected to the door controller and monitoring is enabled Sensor monitoring logic is defaulted to ActiveLow ActiveHigh monitoring logic is selectable via InTestLogic on menu 3 To turn sensor monitoring OFF navigate to menu 3 on the LCD and set InTestMode to OFF WIRING MOUNTING WIRING RED BLACK BROWN B...

Страница 7: ...play active output scroll select 3 Select language before entering the first LCD menu Select Back to return to previous menu or display Select More to go to next level IR menu Radar menu Outputs Diagnostics menu 1 Push to enter the LCD menu displayed value factory value displayed value saved value motion AIR 2 Enter password if necessary Not during the first minute after power on of the sensor HOW...

Страница 8: ...djustment session always lock the sensor Enter the existing code x number of flashes corresponds to the remote control button assignment for the current setting see page 16 for parameter assignments Example For a sensor still programmed to factory default the value check for AIR Presence Time will result in 2 green LED blinks full reset partial reset It is recommended to use a different access cod...

Страница 9: ...trol you can also press the RAD Fieldsize button and the plus sign to select Wide shape or the minus sign to select Narrow shape To check the existing radar field size shape use the following sequence Tilt the antenna up to adjust the depth outward and down to adjust inward from the doorway x number of flashes corresponds to the field size 1x narrow 2x wide Navigate to menu 2 of the LCD to choose ...

Страница 10: ...at the curtain placement matches the LCD screen If necessary use visible spots and red adjustment knob to position properly see page 11 UNDERSTANDING THE LCD CURTAINS GRAPHICS GENERAL SETTINGS the number of squares on a line indicates the curtain number i e C1 C2 or C3 the rectangles on each side of the setting number represent sliding door panels THRESHOLD SETTINGS a dotted line indicates that th...

Страница 11: ...D double press OR 2 If necessary adjust the AIR curtain angles using the red adjustment knob Ensure AIR curtain positioning reflects IR Curtains on the LCD screen CLOSER CLOSER AWAY AWAY default 3 When in Threshold mode verify correct positioning of the threshold curtain First turn on the red spots and then verify that either C1 is at least in line with the moving door panel see image below left o...

Страница 12: ...n single slider applications 2 Always verify the actual AIR detection field by walk testing according to ANSI 156 10 Do not use a SPOTFINDER to verify the AIR detection field Additional adjustments are possible by LCD or remote control see OVERVIEW OF SETTINGS ACTIVE INFRARED SAFETY FIELD 1 If desired adjust the field width using the LCD menu or remote control buttons see page 16 IR Width menu WID...

Страница 13: ...he LED will flash white confirming the synchronization is detected If an overlapping safety field is found in the threshold of the door ULTIMO will remain synchronized for 2 minutes while the door is closed If activation does not occur for 2 minutes the white LED will flash confirming synchronization is lost The fields will be synchronized again upon the next activation and will be confirmed by a ...

Страница 14: ... LCD will display the camera icon and the LED will slowly flash red green and then turn off slow flash PUSH BUTTON Press the gray knob twice REMOTE CONTROL Use the following remote control button sequence Ensure that the infrared field is clear of any obstructions Test the proper operation of the system installation before leaving the premises ...

Страница 15: ...anced IR PresTime 30 sec 1 min 2 min 5 min 10 min 20 min 60 min infinite IR Freq auto synch IXIO 1 freq A 2 freq B 2 IR Startup yes no RADAR SETTINGS Rad Fieldsize small large Rad Shape LCD narrow and wide setting options Remote Control After pressing the Rad Fieldsize button use the plus sign button to select the Wide shape or the minus sign button to select the Narrow shape Numeric remote contro...

Страница 16: ... received on curtain 1 IR C2 Energ signal amplitude received on curtain 2 IR C3 Energ signal amplitude received on curtain 3 IR ReactTime reactivity speed of infrared in relation to immunity and environment PowerSupply supply voltage at power connector Reset log no yes FactoryRst 2 full partial SETTINGS cont NOTES 1 The sensor LED will briefly flash RED during monitoring communication with the doo...

Страница 17: ...TTINGS password 1234 Config P N configuration file identifier Soft P N software version identifier Operating Time power duration since first startup TempSensor degrees in Celsius Password LCD and remote control password 0000 no password SETTINGS cont ...

Страница 18: ...ST is ON in the sensor settings Sensor malfunction Replace the sensor RED Visible External Monitoring Test Indication LED flashes continuously Wiring issue Verify wiring Door control not set correctly Verify door control monitoring set to correct test logic according to the door control LT1 Assisted Setup Error IR Curtain set to 1 2 4 or 5 C2 and or C3 interfering with door during closing cycle In...

Страница 19: ...oltage in Diagnostics menu menu 3 of the LCD Check wiring 3 E3 orange LED flashes 3 times Radar communication error Check the connection at the radar 4 E4 orange LED flashes 4 times The sensor does not receive enough AIR energy Ensure proper mounting height Turn on the visible red spots and adjust the angle of the AIR curtains Deactivate curtain 3 C3 outer curtain 5 E5 orange LED flashes 5 times T...

Страница 20: ...estrian doors IDA certified for doors gates and factory trained for the type of door gate system Installers and service personnel are responsible for executing a risk assessment following each installation service performed ensuring that the sensor device system performance is compliant with local national and international regulations codes and standards Once installation or service work is compl...