CONNECT THE OIL LINE

Gravity System:

The oil burner is normally equipped with a single-stage pump equipped 

for one line (gravity) flow. Use 

3

8

" O.D. or larger soft copper tubing and attach with flared

fittings. DO NOT USE COMPRESSION FITTINGS. Install the shut off valve and oil filter in the
oil line. Follow instructions from the pump manufacturer (attached to pump).

Lift System:

Run a two-line system (suction and return lines) for lifts over 8 feet. Install a 

bypass plug if required according to the instructions attached to the pump. (Plug is in bag
with instruction sheet.) The burner may be ordered with a two-stage pump for high lifts or
longer runs.

WARNING!!! When you install the bypass plug you MUST run a two-line system!

For any horizontal run or lift that exceeds the maximum length specified in the chart below, 
a booster pump must be used. Booster pumps may be obtained from Sun Tec Hydraulics, Rock-
ford, Illinois. Booster pumps must be installed as close to the oil supply tank as possible. Suc-
tion and return lines should be the same diameter and both go within 6" of the bottom of the
tank. The return line should stop slightly above the suction line. Use a minimum of fittings.
Make tubing bends with as large a radius as possible. DO NOT USE COMPRESSION FITTINGS.
Use caution in the final connection to the burner. Do not put strain on the fuel unit. Before 
attaching tubing to the burner, form a coil in the tubing to minimize any vibration. Bury oil
lines in the floor for quiet operation, making sure there are NO CONNECTIONS OR FITTINGS
UNDER THE FLOOR.

MAXIMUM LIFT AND HORIZONTAL RUN 

(Refer to pump manufacturer’s instructions)

Maximum Lift & Horizontal Run for Oil Units

Two-pipe System with

Two-pipe System with

One-pipe System

Single-Stage pump*

Two-Stage pump**

Lift

Horizontal Run

Lift

3450 RPM

Lift

3450 RPM

3

8

" O.D. Tube

1

2

" O.D. Tube

3

8

" O.D. Tube

1

2

" O.D. Tube

3

8

" O.D. Tube

1

2

" O.D. Tube

0'

65'

100'

0'

84'

100'

0'

93'

100'

4'

45'

100'

1'

78'

100'

2'

85'

100'

7'

31'

100'

2'

73'

100'

4'

77'

100'

8'

16'

64'

3'

68'

100'

6'

69'

100'

Inlet vacuum must not exceed 6 inHG

4'

63'

100'

8'

60'

100'

on a one-pipe system

5'

57'

100'

10'

52'

100'

6'

52'

100'

12'

44'

100'

7'

47'

100'

14'

36'

100'

8'

42'

100'

16'

27'

100'

9'

36'

100'

18'

76'

10'

31'

100'

*Suntec A Series pumps

11'

26'

100'

**Suntec B Series pumps

12'

21'

83'

Inlet vacuum must not exceed 6 inHG

13'

62'

on a one-pipe system. On a two-pipe

14'

41'

system, inlet vacuum must be less than
12 inHG for “A” model pumps and 
17 inHG for “B” model pumps.

Содержание Oil-Fired

Страница 1: ...ter temperature is needed in part of the water system automatic temperature limiting devices must be used on all lines to water taps WARNING Flammable vapors may be drawn to this water heater from oth...

Страница 2: ...40 126 9 3 4 3 4 1 90 136 61 20 6 54 18 120 60 305 51E BCS 50 152 1 1 1 1 1 90 161 59 24 6 11 18 120 60 345 120E BCS 113 155 1 1 1 2 2 90 163 67 311 2 6 19 22 120 60 705 190E BCS 113 190 1 35 1 2 2 90...

Страница 3: ...ally out of the west or north is the preferred wall for installa tion This reduces the likelihood that the Balanced Flue application will be operating against high winds and severe cold when it is cyc...

Страница 4: ...EMENT NOTE Locate the heater so it is not subject to physical damage from moving vehicles or flooding DO NOT INSTALL THE WATER HEATER ON COM BUSTIBLE FLOORING Place on noncombustible flooring and main...

Страница 5: ...d up in the water heater and result in tank failure If this water heater is installed in a closed system or if backflow preventers and pressure regulators are installed a properly sized expansion tank...

Страница 6: ...astat with immersion well is packed with the burner The thermostat is factory set at 120 F for residential use The maximum setting for 20 32 40 and 51E BCS models is 160 F for 120 and 190E BCS models...

Страница 7: ...eturn line should stop slightly above the suction line Use a minimum of fittings Make tubing bends with as large a radius as possible DO NOT USE COMPRESSION FITTINGS Use caution in the final connectio...

Страница 8: ...to see that the burner control locks out in the time specified on the control Reattach the wire and reset the control The burner should restart Note You may have to wait a minute before resetting the...

Страница 9: ...lter and have the oil tank checked for sediment Clean the tank if necessary 4 The system should be checked with combustion instruments for safe and efficient operation 5 Keep the oil tank full to prev...

Страница 10: ...tes runs for a short time 10 20 seconds and then goes out on safety replace the flame detector If the burner still runs only a short time replace the control 6 If you smell oil or combustion products...

Страница 11: ...120E BCS Carlin 1 1 x 70A 190E BCS Carlin 1 35 x 70B The only controls acceptable for use with these models are as follows For normal household applications Burner Carlin EZ1 with 15 minute post purge...

Страница 12: ...ntal or consequential damages so the above limitations or exclusions may not apply to you This warranty gives you specific legal rights and you may also have other rights which vary from state to stat...

Страница 13: ...Oil Fired BCS Page 13 BOCK OIL FIRED WATER HEATER...

Страница 14: ...Page 14 Oil Fired BCS Balanced Flue BURNER WIRE DIAGRAM Models 20 32 40 51 120 190E BCS Carlin EZ Temp Control...

Страница 15: ...Oil Fired BCS Page 15 EXPANSION TANK OPTIONAL IF ANY OF THESE DEVICES ARE USED A PROPERLY SIZED EXPANSION TANK MUST BE INSTALLED...

Страница 16: ...h space and water Bock Radiant uses functional hot water and avoids boiler type overheating that wastes energy Bock Radiant eliminates using a boiler during warm months and lets ecomonic domestic hot...

Отзывы: