Programming manual SCU-series
HB-37500-820-10-12F-EN SCU Programming manual
Page 170 of 252
Status: 19.03.2021
Timer
Function block that starts a meter in case of an edge change. After the fixed time lag, the
result is “1” or “0”.
Figure 157
properties window „Timer“
Block-ID: Timer number. The timer number can be set when the timer is plugged in. If all timers are
used, the timer command in the menu is disabled.
Delay: desired period, during which the timer shall run.
T min
=
16 ms
T max
=
2592.000.000ms
43.200min
720h
NOTICE:
The programmable values equal an integral multiple of the cycle time!