INSTALLATION
Unpacking
Preparing
the
Installation
Site
Power
Environmental
Compare the unit and serial number of the equipment you received to the packing slip located on the
outside of the box. Inspect equipment carefully for damage that may have occurred in shipment. If there is
damage to the equipment or if materials are missing, contact BayTech Customer Support at
228-563-7334
or call toll free inside the United States at
800-523-2702
. At a minimum, you should receive the
following:
1.
The MMP unit.
2.
Paper insert referencing BayTech’s website a
www.baytech.net/support/ftp_series.php
.
3.
1 ea. DE-9 (9 pin) PC com port adapter -- 9FRJ45PC (with Cisco Interface) or 9FRJ45PC-1.
4.
1 ea. RJ-45 Roll over cable -- RJ08X007.
5.
1 set of (Tool-less hardware installed and Vertical Brackets, M140C138) or Horizontal Brackets --
M140R114, M140R115
NOTE:
Keep the shipping container and packing material in the event future shipment is required.
The installation area should be clean and free of extreme temperatures and humidity. Allow sufficient
space behind the MRP/MMP/MSP/MDP unit for cabling and receptacle connections. Access to installation
site should be restricted to authorized personnel. Installation of these units should be limited to ITE and
Telco server environments.
PRÉPARATION DE L'EMPLACEMENT D'INSTALLATION
Le secteur d'installation devrait être propre et exempt des températures et de l'humidité extrêmes.
Permettez le suffisamment d'espace derrière l'unité de MRP/MMP/MSP/MDP pour des raccordements de
câblage et de réceptacle. L'accès à l'emplacement d'installation devrait être limité au personnel autorisé.
L'installation de ces unités devrait être limitée à ITE et à environnements de serveur de Telco.
120V VAC Model:
INPUT
120 VAC 50/60 Hz,
MAXIMUN LOAD
(15, 20, 30Amps);
OUTPUT:
NEMA 5-15/20R 120VAC, 20A
208V VAC Model:
INPUT:
208 VAC 50/60 Hz,
MAXIMUN LOAD
(15, 20, 30, 50 or
60 Amps);
OUTPUT:
IEC302 C13s 208VAC 10A, C19s 208VAC 16A
230VAC Model:
INPUT:
230VAC, 3Ø, 50/60 Hz,
MAXIMUN LOAD
(10,.16, 20, 30,
32, 60Amps);
OUTPUT:
IEC302 C13s 230VAC 10A, C19s 230VAC 16A
120/208V 3øY VAC Model:
INPUT:
120/208 VAC, 3Ø, 50/60 Hz,
MAXIMUN LOAD
(20, 30, 50 or 60 Amps);
OUTPUT:
NEMA 5-15/20R 120VAC 20A, IEC302 C13s
208VAC 10A, C19s 208VAC 16A;
208V 3ø
∆
VAC Model:
INPUT:
208 VAC 50/60 Hz,
MAXIMUN LOAD
(20, 30, 50 or
60 Amps);
OUTPUT:
IEC302 C13s 208VAC 10A, C19s 208VAC 16A
230/400V 3øY VAC Model:
INPUT:
230/400 VAC, 3Ø, 50/60 Hz,
MAXIMUN LOAD
(16, 20, 30, 32, 60 Amps);
OUTPUT:
IEC302 C13s 230VAC 10A, C19s 230VAC 16A
Temperature Range: 32
⁰
- 131
⁰
Fahrenheit
(0
⁰
– 55
⁰
Celsius)
Humidity: 5-95% Relative Humidity
Max Altitude: 10,000 Feet (3048 Meters)