background image

 

Page

56 

Power

 

Factor

 

Threshold

 

Menu

 

 
 
 
 
 

Individual

 

Units

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 
 

 

Breaker List for device 1, MMP-27 
Ckt   PF Threshold (%)   Pwr Threshold (W) 
 1         100                    10 
 2         100                    10 
 3         100                    10 
 4         100                    10 
 5         100                    10 
 6         100                    10 
 
Enter Request :1

 

Parameters to control generation of SNMP traps based on
circuit Power/VA power factor and minimum power level 
 
Sel  M/P    Identifier     Circuits    Outlets 
1    2/1    MMP27              6         24 
2    All Circuits/Outlets - Power Factor Threshold 
3    All Circuits/Outlets - Power Threshold 
 
Enter Request :1 
 

Circuit Power Factor Thresholds....1 
Outlet Power Factor Thresholds.....2 
 
Enter Request :1

 

Select 1),

 to display either Circuit or 

Outlet Power Factor (PF)   

Unit displays breaker list of circuits. 
Select the Circuit number to change 
the threshold values 

Select 9), from the RPC Management Menu,

 to display the unit’s power efficiency on the web 

page and through SNMP. The user sets a minimum power level that will send an SNMP trap to the 
SNMP Manager. The smaller the power factor, less than (1), more current is needed (wasted) to do 
the same amount work  

M/P

 = Module port,  

Identifier

 = Unit Id,  

Circuits

 = number of circuits on unit.  

Outlets

 = number of unit outlets. 

Select 1);

 to display current Power 

Factor (PF) and Power Threshold 
settings for each individual unit 
circuit.  

Breaker Circuit Threshold Menu 
Device 1, Breaker Circuit 1 
Efficiency Threshold: 100, Power Threshold: 10 
 
  Power/VA Power Factor Threshold....1 
  Minimum Power Threshold............2 
 
Enter Request :1

 

Unit displays the Breaker Circuit 
Threshold Menu with circuit breaker 
number and current values. 
 

Select 1),

 to change the Power Factor 

Threshold level. Enter a per cent value 
(%). 

Factory Default is (0%).

 

Power/VA ratio threshold as a percent, between 0 and 100, 
inclusive. Power factors below this value will generate an SNMP 
trap, if enabled and power is above minimum power threshold.  A 
value of 0 disables threshold. 
 
  Enter threshold value: 

NOTE:

 The Power Factor Threshold SNMP alarm is sent only if both respective values drop 

below the Power Factor Threshold and Power Threshold at the same time. 

Содержание MMP

Страница 1: ...2019 Copyright 2019 Bay Technical Associates Inc 1 1 2019 Modular Metered Power MMP ...

Страница 2: ... NETWORK MENU 21 OUTLET CONTROLLER STATUS SCREEN 22 OUTLET HELP OPTIONS 23 RECEPTACLE CONTROLS 23 ON OFF REBOOT LOCK AND UNLOCK 23 STATUS 24 OSTATUS 24 OUTLET CONTROL CONFIGURATION MENU 25 Manage Users 25 Change Outlet Name 28 Enable Disable Confirmation 28 Enable Disable Status Menu 29 Change Unit ID 29 Change Alarm Threshold 29 Change Display Orientation 30 DISPLAY CURRENT ELECTRICAL CHARACTERIS...

Страница 3: ... Enable Disable 46 Telnet Enable Disable 46 SSH Enable Disable 47 SSH Host Key Generation 47 IP Filter Configuration 47 SNMP Configuration 48 Web Server Configuration 49 MODULE NAME 50 RPC MANAGEMENT 50 Temperature Alarm Threshold 50 Under Voltage Alarm Threshold 51 Over Voltage Alarm Threshold 51 Low Current Alarm Threshold 51 Environmental Sensors 51 Outlet Groups 52 Temperature Units degrees C ...

Страница 4: ...__________________________________________________________ 19 Figure 12 Network Manage Users _____________________________________________________________________________ 20 Figure 13 Network Port Configuration __________________________________________________________________________ 20 Outlet 1 Control Help________________________________________________________________________________________ 2...

Страница 5: ...is term is used to denote items of interest to the user cr Carriage Return or ENTER The information in this document is subject to change without notice The statements configurations technical data and recommendations in this document are believed to be accurate and reliable but are presented without express or implied warranty Users must take full responsibility for their applications of any prod...

Страница 6: ...our products and we hope that you will continue to look to BayTech for your remote management needs BayTech s Modular Series unit provides a Serial EIA232 interface that controls user access and outlet controls to the power strip CAUTION All power should be removed from the BayTech unit prior to removing or installing cables and or adapters The RPC has an RJ 45 port which uses an 8 pin crossed mod...

Страница 7: ...lation of these units should be limited to ITE and Telco server environments PRÉPARATION DE L EMPLACEMENT D INSTALLATION Le secteur d installation devrait être propre et exempt des températures et de l humidité extrêmes Permettez le suffisamment d espace derrière l unité de MRP MMP MSP MDP pour des raccordements de câblage et de réceptacle L accès à l emplacement d installation devrait être limité...

Страница 8: ...ipment To protect from such power surges and spikes this unit must have a good earth ground or good power surge protection ATTENTION Les montées subites et les transitoires à haute tension peuvent endommager cet équipement Pour se protéger contre de telles montées subites et transitoires de puissance cette unité doit avoir une bonne protection rectifiée ou bonne de la terre de puissance de montée ...

Страница 9: ...ing on if the unit has circuit breakers in the case of power overload the circuit breaker automatically trips Determine the cause of the tripped circuit breaker correct the problem then reset the circuit breaker by depressing the circuit breaker switch If an overload condition occurs the MRP MMP MSP MDP status menu is still accessible If all circuits are closed the circuit breaker status menu will...

Страница 10: ...mit Data Out 5 RX In Receive Data In 6 N C In No Connection 7 GND Signal Ground 8 DCD In DCD into the MMP Adapter signals Listed are the pin specifications for the BayTech cable and adapters and the terminal COM ports Serial 1 Port Pin Out Table Signal RS 232 Port DS RS 232 Port MMP COM Port DE 9 Pin COM Port DB 25 Pin Signal DTR 1 1 4 20 DSR GND 2 2 1 GND RTS 3 3 7 5 CTS TXD 4 4 3 2 RXD RXD 5 5 2...

Страница 11: ...8X007 Pin out Serial 3 RJ45 Receptacle Plug Adapters Serial 4 9FRJ45PC Cisco Adapter Pin Out Serial 5 9FRJ45PC 1 Adapter Pin out Use with RJ08X007 Cable only if controller has a B C and is set to C Use with RJ08X007 Cable Without B C switch or With B C switch set to B ...

Страница 12: ... the unit s receptacles An illuminated LED signifies the corresponding outlet has power turned on thus the attached equipment has power to it No lit LED signifies no power to the receptacle IMPORTANT If you send the command to reboot a receptacle with a host terminal or modem attached active connection to that terminal or modem is lost and will have to be reestablished IMPORTANT An assigned user i...

Страница 13: ...milar to Figure 4 7 Select number for the Manage Users option You should see a menu similar to Figure 5 8 IMPORTANT NOTE the first user added will be the ADMIN user Type A and press Enter Type the name of the admin user The name is case sensitive 9 Select the user number You should see the user in the menu similar to Figure 6 10 Select Add Outlet s to add a few outlets i e 1 2 4 and press Enter or...

Страница 14: ...Enter until you are asked to Accept Changes Type Y to accept changes or N to decline changes 13 After Accepting or Declining Changes you should get the Network Access Menu Figure 7 14 Select Unit Reset to update the external connections Once the reset is completed 1 minute connect the Baytech device to your network using an Ethernet cable 15 If you disabled the DHCP in step 11 you should see a men...

Страница 15: ... F Switch 1 Open 2 Open 1 MOD 1 Outlet 1 On 2 MOD 1 Outlet 2 On 3 MOD 1 Outlet 3 On 4 MOD 1 Outlet 4 On 5 MOD 2 Outlet 1 On 6 MOD 2 Outlet 2 On 7 MOD 2 Outlet 3 On 8 MOD 2 Outlet 4 On 9 MOD 3 Outlet 1 On 10 MOD 3 Outlet 2 On 11 MOD 3 Outlet 3 On 12 MOD 3 Outlet 4 On 13 MOD 4 Outlet 1 On 14 MOD 4 Outlet 2 On 15 MOD 4 Outlet 3 On 16 MOD 4 Outlet 4 On 17 MOD 5 Outlet 1 On 18 MOD 5 Outlet 2 On 19 MOD ...

Страница 16: ...e current user password Whoami cr Displays the current user name Unitid cr Displays the unit ID Type Help for a list of commands MMP 11 MMP password Enter new Password Re Enter new Password Type Help for a list of commands MMP MMP config Unit ID MMP11 1 Manage Users Add Delete Rename assign outlets 2 Change Outlet Name Select an outlet to change its name 3 Enable Disable Confirmation Confirmation ...

Страница 17: ...lowing menu appears if the unit has been reset or initial setup User Assigned Outlets C1 1 C1 2 C1 3 C1 4 A Add User D Delete User R Rename User C Change Circuit Group Enter user number to assign Outlets A D C or R Enter Request NOTE User in position 1 will be the admin user for the outlets Older units will not display the delete option until a user is added Select A Add user from the User Managem...

Страница 18: ...ables Disables the confirmation of choices Example Turn off all outlets Y N Enable Disable Status Menu Enables Disables whether outlet status menu is displayed Change Unit ID Allows the user to change the name of the unit The defaulted is something similar to MMP1 Allows the user to personalize or customize name or location up to 31 alphanumeric characters Change Alarm Threshold The Alarm Threshol...

Страница 19: ...eby preventing unwanted port disconnection Connect Port ID Echo 6 Echo port name or module port Login Setup 7 Login Menu Serial Telnet Radius TACACS access control manage users Network Port Configuration 8 Network Port IP Address Module Name 9 Change name of module MMP Management 10 Set up Voltage Current Sensor threshold Firmware Config Download 11 Update Firmware SSL Configuration files Exit X C...

Страница 20: ...ubnet Mask and Gateway Address or enable the DHCP The Changes must be saved and the module reset for network changes to take effect Network setup Ethernet Address 00 C0 48 00 01 FD IP Address 70 150 140 89 Subnet Mask 255 255 255 224 Default Gateway 70 150 140 65 Connection Inactivity Timeout mins Disabled Carriage Return Translation Enabled Break Length msecs 350 DHCP is Disabled Telnet is Enable...

Страница 21: ...eset RU Logout T Enter Request Universal RPC login root Password BAYTECH For further information check http www baytech net opening access to internal RPC MMP 11 Series C 2008 BayTech F2 01 Option s Installed True RMS Voltage True RMS Current Internal Temperature After logging into the unit the unit will display additional hardware information Outlet controller firmware F1 11 Options installed Vol...

Страница 22: ...On 18 MOD 5 Outlet 2 On 19 MOD 5 Outlet 3 On 20 MOD 5 Outlet 4 On 21 MOD 6 Outlet 1 On 22 MOD 6 Outlet 2 On 23 MOD 6 Outlet 3 On 24 MOD 6 Outlet 4 On Type Help for a list of commands MMP 11 NOTE Int Temp unit internal temperature Ext external temperature probe Two environmental ports are available Temperature reads in Fahrenheit or Celsius RH Relative humidity NOTE The user will see only those out...

Страница 23: ...t 3 type ON 3 from the MMP prompt If the confirmation option is turned on the MMP will display the following Turn On Outlet 3 Y N Type Y for yes or N for no Likewise typing ON ALL ON 0 or ON at the MMP prompt and responding Y for yes turns On all outlets The OFF n command works similarly as the ON n command The REBOOT n command will reboot or reset equipment attached to corresponding receptacle s ...

Страница 24: ...18 0 V 0 W 4 VA On CKT 4 Outlet 5 0 0 A 0 2 A 118 0 V 0 W 4 VA On CKT 5 Outlet 1 0 0 A 0 2 A 118 0 V 0 W 4 VA On CKT 5 Outlet 2 0 0 A 0 2 A 118 0 V 0 W 4 VA On CKT 5 Outlet 3 0 0 A 0 2 A 118 0 V 0 W 4 VA On CKT 5 Outlet 4 0 0 A 0 2 A 118 0 V 0 W 4 VA On CKT 5 Outlet 5 0 0 A 0 2 A 118 0 V 0 W 4 VA On CKT 6 Outlet 1 0 0 A 0 2 A 118 0 V 0 W 4 VA On CKT 6 Outlet 2 0 0 A 0 2 A 118 0 V 0 W 4 VA On CKT 6...

Страница 25: ...ber to assign Outlets A D C or R Enter Request NOTE the first assigned user will be the admin user for the outlets Older units will not display the delete option unit a user is added NOTE If the Add user option is NOT present than the maximum number of users have been assigned You will get a message saying No more users can be added User Assigned Outlets C1 1 C1 2 C1 3 C1 4 1 Engineer N Y N Y A Ad...

Страница 26: ... not had a power cycle or unit reset command performed recently before you delete the user in the first position perform a unit reset command from the main menu This action will prevent the unit from having NO Admin user assigned even though the first position user was deleted and there is a second user assigned If the NO Admin condition occurs reset the unit to factory defaults User Assigned Outl...

Страница 27: ...Enter Outlet number s Type the number of the outlet to be removed from the user s access For example if you want to remove Outlet C1 2 enter the number 2 followed by cr If you want engineer to have access to Outlets C1 2 C1 3 and C1 4 enter the numbers 2 3 and 4 separated by commas followed by cr The unit redisplays the Assigned Outlet Menu of the user with an N for the outlets NOT assigned User A...

Страница 28: ...equest 1 Type the number of the outlet to be changed For example to change the name of Outlet 4 type the number 4 at the Enter Request prompt followed by cr The unit will ask if you want to modify the current name Type N to keep the same name or type Y to change the name Y will cause the unit to prompt for a new name Current Outlet Outlet 4 Modify Y N y Enter Type a new receptacle name maximum 16 ...

Страница 29: ...rcuitry 1 Circuit Breaker Alarms 2 Module Group Circuit Breaker Alarms If the number of circuit breakers equals the number of modules the unit will display the following Circuit C1buzzer alarm value 12 0 Amps Modify Y N y Enter 2 0 Type N to keep the current value or type Y to change the value and enter the new value followed by Enter and the unit will display next circuit group Circuit C2 buzzer ...

Страница 30: ...r Normal Display Y N y Type N to keep the current value or type Y to change the value and enter the new value press Enter and the unit will display next circuit group Circuit breaker 1 buzzer alarm value 12 0 Amps Modify Y N y Enter 15 Circuit breaker 2 buzzer alarm value 12 0 Amps Modify Y N y Default setting is 12 0 Amps Select 1 Circuit Breaker Alarms changes the alarm level per circuit breaker...

Страница 31: ...sword NOTE If you do not have the user s current password delete the user Reinstall user Select option to change password and the unit will respond asking for a new password Type Logout Logoff or Exit at the prompt to logoff from the unit This will close the Outlet Control session Press Enter to open the Outlet Controller session A login prompt may appear if a user has been assign to an outlet New...

Страница 32: ...en 0 Press ENTER to continue Select 2 Network Status contains the MAC address IP address Mask TX RX packets and their status C configuration user current process Active Users USER FROM INTERNAL CONN STATUS PID 1 root localhost Normal 23 C 2 root 70 150 140 69 Normal 490 3 root 70 150 140 66 Normal 492 Strike T CR to terminate a connection process CR to continue Select 3 shows the name of the user ...

Страница 33: ... Iface interface used to reach the network gateway in this case Baytech network card Kernel IP routing table Destination Gateway Genmask Flags Metric Ref Use Iface 192 168 2 0 255 255 255 0 U 0 0 0 eth0 127 0 0 0 255 0 0 0 U 0 0 0 lo default 192 168 2 1 0 0 0 0 UG 0 0 0 eth0 Press ENTER to continue Select 7 to see a list of Process commands used by the firmware to operate Type T and the unit will ...

Страница 34: ...0 Set up Voltage Current Sensor threshold Firemware Config Download 11 Upload FTP firmware upload and download unit configuration Exit X CR Enter Request NOTE The following message Configuration mode in use signifies a user in the other port is in the Configuration menu Installed Modules 01 Attention Character is Disconnect Time Guard is Disabled Port ID Echo is Disabled Module Name is Universal R...

Страница 35: ...d through the phone line via a modem The default settings are 9600bps 8 data bits no parity one stop bit RTS and DTR High IMPORTANT Communications with the terminal computer connected to the port will be lost until the serial port configuration of the terminal computer matches the unit s serial port Port Device Device Baud Word Stop Parity Handshake LineDrive Type Name Rate Size Bits DTR RTS 1 RS2...

Страница 36: ...y it is very likely that these values could be transmitted as data and the transmission would fail Hardware Handshaking This style uses actual hardware lines Like the TX and Rx lines the RTS CTS and DTR DSR lines work together When a receiver is ready for data it will assert the RTS Request to Send line This is then read by the sender at the CTS Clear to Send input indicating it is clear to send t...

Страница 37: ...sed for stop bits the greater the lenience in synchronizing the different clocks but the slower the data transmission rate Parity is a simple form of error checking used in serial communication For even and odd parity the serial port will set the parity bit the last bit after the data bits to a value to ensure that the transmission has an even or odd number of logic high bits For example if the da...

Страница 38: ... access the network main menu Select 4 from the Network Configuration Menu sets the attention character The unit displays the following The Default is a semi colon Attention Character is Enter Attention Character Select 5 from the Network Configuration Menu ensures reliable binary data transmission by providing a one second Timeguard after the unit receives the attention character If more data is ...

Страница 39: ...sable prompt Press Enter to keep same setting Login prompt for serial is Disabled Enable Y N CR for no change If the login has been enabled you will get a prompt similar to the following The default user and password is root and baytech all lower case Universal RPC login root Password Select 2 from the Login setup Menu to allow the administrator to add delete users and change their passwords for m...

Страница 40: ...1 Exit X Enter Request 1 Select 1 to change a user s password The unit displays the following menu User name root Enter old password CR if none If the user does not have a password the RPC will respond for a new password and a confirmation to re enter the new password Enter new password 31 characters Confirm by re entering new password Password change successful Select D Delete user The unit re di...

Страница 41: ...er IP addresses Select 4 Radius Secret sets the shared radius secret A secret can be up to 16 characters and must be exactly the same as the secret stored on the server Select 5 Enable URPC usernames as backup enables URPC usernames as backup login allows an unsecured access until the RADIUS server becomes available Select 6 Radius Login Timeout sets the amount of time the unit will wait for a res...

Страница 42: ...6 Enable Disable encryption TACACS login Timeout 7 Sets Time units waits for response TACACS Server Port 8 Assign secure TCP port URPC Privilege Level Enable 9 Enable Disable TACACS privilege URPC Privilege Level 10 Set Privilege Level 1 15 Exit X CR Select 4 from the Login Setup Menu displays the TACACS Configuration menu Setting up TACACS To enable TACACS for logins do the following Enable TACAC...

Страница 43: ...el Enable enables the unit to send a privilege level to the TACACS server Default is Disabled Select 10 URPC Privilege Level assigns privilege levels 1 is the minimum user privilege and 15 is the root admin privilege level Default is 15 Example of operation Privilege Level enabled set to 10 In tacacs conf file on daemon user1 is configured for exec priv lvl 9 user2 is configured for exec priv lvl ...

Страница 44: ...provides a message format for communication between a computer and your devices and Web Server Configuration allows web access and sets up options for each Network setup Ethernet Address 00 C0 48 00 01 FD IP Address 70 150 140 89 Subnet Mask 255 255 255 224 Default Gateway 70 150 140 65 Connection Inactivity Timeout mins Disabled Carriage Return Translation Enabled Break Length msecs 350 DHCP is D...

Страница 45: ... form Enter Subnet Mask in dotted decimal form This option is for setting the IP Version 6 The menu options are IPv6 Address Network Prefix Size and Gateway Ethernet Address 00 C0 48 0C A6 C6 IPv6 Address 0 IPv6 Default Gateway IPv6 Address 1 Network Prefix Size 2 Gateway 3 Enter Request The IPv6 address is a 128 bit network address assigned by your network manager for your network The IPv6 Addres...

Страница 46: ...rom Network Port Configuration Menu to enable or disable the DHCP feature Dynamic Host Configuration Protocol DHCP is a communications protocol that lets network administrators manage centrally and automate the assignment of Internet Protocol IP addresses in an organization s network Default setting is ENABLED Select 8 from Network Port Configuration Menu to enable or disable the Telnet feature Te...

Страница 47: ...n Menu the IP Filter Management Menu allows the admin user to pass or block certain IP Addresses If you have no rules defined the unit may display only options A E C Select 10 from Network Port Configuration Menu to allow the user to generate a unique SSH host key for the RPC unit This key is part of the SSH encryption process Each RPC leaving Baytech is shipped with same default SSH host key It i...

Страница 48: ...NMP program Information provided is for the SNMP Agent only Baytech Support will assist with the Agent part only For SNMP Manger assistance refer to the vender manual or contact the vender of the SNMP software you are using NOTE There are a number of shareware MIB Browsers that can be downloaded from the internet to make changes and receive traps for a quick verification test NOTE To use the SNMP ...

Страница 49: ...P Address 192 168 1 102 Enter new Trap Host IP Address SNMP Trap Host 4 IP Address 192 168 2 136 Enter new Trap Host IP Address Read Gives read access to authorized management stations to all objects in the MIB except the community strings but does not allow write access Write Gives read and write access to authorized management stations to all objects in the MIB but does not allow access to the c...

Страница 50: ...age have administrator privilege unless a TACACS server and privilege levels are used for authentication IMPORTANCE If a user is still connected to the outlet controller menu or the user does not properly release the controller the Web page will not update Module Name is RPC Enter Module Name 32 chars max Select 9 from the Network Configuration menu to change the unit name Select 1 to change the a...

Страница 51: ...Sel M P Identifier Hi V Lvl 1 2 1 MMP10 1300 Select 4 to change the alarm for low current Enter the Selection Sel Number and press Enter Type a value in tenths of a volt i e 100 10 0 amps Sel M P Identifier Low Curr 1 2 1 MMP10 0 Enter voltage threshold value in tenths of a volt Enter low current threshold value in tenths of an amp NOTE M P Module number and Port number Identifier this unit s mode...

Страница 52: ... 4 enable the SNMP traps to be sent if the corresponding threshold had been exceeded NOTE NP No Probe detected NOTE The type Contact signifies the unit does not recognize or detect a probe but still be able to send SNMP Traps Group Name Outlets 1 Router GP A 2 1 1 2 1 2 2 1 3 2 1 4 2 Server Row 2 1 5 2 1 6 2 1 7 2 1 8 3 Radius 2 1 9 2 1 10 2 1 11 2 1 12 4 Server backup 2 1 13 2 1 14 2 1 15 2 1 16 ...

Страница 53: ...outlet Delete ALL outlet groups Y N y The unit displays the following and asks for a name for the new Group Select 3 to delete a specific outlet group select the number of the group to be deleted The unit will display Group Deleted Select 4 to rename an outlet group s name select the number of the group to be renamed The unit displays the selected group and prompts for a new name Select 5 to modif...

Страница 54: ...feature NOTE Read the instruction carefully for the feature to operate properly RPC Cascade Mode is Enabled Enabling this feature will allow access and management of a BayTech Remote Power Device through the console EIA 232 port via telnet ssh SNMP http In RPC Cascade Mode normal console port terminal service will operate only when the network cable is disconnected When Cascade Mode is changed URP...

Страница 55: ... Outlet 2 15 3 MOD 4 Outlet 3 16 3 MOD 4 Outlet 4 Slave Unit Outlets 17 3 MOD 1 Outlet 1 18 3 MOD 1 Outlet 2 19 3 MOD 1 Outlet 3 20 3 MOD 1 Outlet 4 21 3 MOD 2 Outlet 1 22 3 MOD 2 Outlet 2 23 3 MOD 2 Outlet 3 24 3 MOD 2 Outlet 4 25 3 MOD 3 Outlet 1 26 3 MOD 3 Outlet 2 26 3 MOD 3 Outlet 3 28 3 MOD 3 Outlet 4 29 3 MOD 4 Outlet 1 30 3 MOD 4 Outlet 2 31 3 MOD 4 Outlet 3 32 3 MOD 4 Outlet 4 CMD With Ca...

Страница 56: ...NMP Manager The smaller the power factor less than 1 more current is needed wasted to do the same amount work M P Module port Identifier Unit Id Circuits number of circuits on unit Outlets number of unit outlets Select 1 to display current Power Factor PF and Power Threshold settings for each individual unit circuit Breaker Circuit Threshold Menu Device 1 Breaker Circuit 1 Efficiency Threshold 100...

Страница 57: ...SNMP power factor trap if power factor is below threshold Enter threshold value Circuit Power Factor Thresholds 1 Outlet Power Factor Thresholds 2 Enter Request 1 The unit displays the number of outlets on the unit Select an outlet number to change the values for Power Factor PF Threshold and Power Threshold Outlet Circuit Threshold Menu Device 1 Outlet 1 Efficiency Threshold 100 Power Threshold 1...

Страница 58: ...r factors below this value will generate an SNMP trap if enabled and power is above minimum power threshold A value of 0 disables threshold Value will be applied to all circuits and outlets MMX units Enter threshold value This option allows user to set all circuits and outlets to the same Power Threshold levels MMX refers to the metered outlet modular series Default Value 50w Minimum power require...

Страница 59: ...irmware upgrade Waiting to receive compressed image file Selecting Y for yes the unit will display the following as it waits for the firmware file At this point follow the FTP program instruction to transfer the firmware into the unit Select 2 to allow the admin to upload an SSL Certificate to the unit via FTP The filename of the certificate must be ssl pem An SSL certificate is used by the unit t...

Страница 60: ...UNIT WILL RESET AFTER CONFIGURATION IS COMPLETE Enable Configuration File Upload Y N Waiting to receive configuration file At this point FTP the file into the unit A successful file upload and the unit will display configuration file valid updating ds62 configuration ds62 host configuration complete polling rpcs Found RPC at mod 2 port 1 rpc polling complete configuring rpcs Unsuccessful file uplo...

Страница 61: ...uration file to be retrieved via ftp Enable Configuration File Retrieval Y N Select Get Current Configuration File and the unit will display A YES response and the unit will display the following var confupload file created and ready for ftp retrieval Waiting to send configuration file At this point FTP the file to your computer A Successful file retrieval and the unit displays get of configuratio...

Страница 62: ...owing type Y at the prompt The unit will wait for the ASCII file to be transfer via FTP Send file in ASCII file mode Waiting for RC firmware Upgrading RC firmware on RPC at module 2 port 1 Enable update of Relay Controller firmware via Console RS232 port Enabling will reset Ethernet Module when Configuration is exited Enable Firmware Upgrade Y N y Send RC firmware file using ASCII file transfer op...

Страница 63: ...roduct is in excellent condition A product may not be returned after 30 days from the original date of shipment unless approved by BayTech management For additional information or more specific warranty issues contact BayTech s Technical Support or Customer Service Departments at 800 523 2702 or 228 563 7334 This warranty does not cover misuse or minor imperfections that fall within design specifi...

Страница 64: ... Long Beach MS 39560 Telephone 800 523 2702 or 228 563 7334 FAX 228 563 7335 Email support baytech net Website www baytech net Return policy refers to BayTech products purchased and returned for credit or repair A Return Authorization RA number must be obtained in all cases before returning the BayTech product Have the serial number and reason for the return or description of the problem handy Cus...

Страница 65: ...original packaging or similar packaging The warranty does not cover damage sustained during shipment Enclose a letter with name address RA number daytime phone number and description of the problem c Mark the RA number clearly on the outside of the package d Ship the unit by insured prepaid carrier to the following address Bay Technical Associates 5239 A Avenue Long Beach Industrial Park Long Beac...

Страница 66: ...ated by the TACACS server Case 3 TACACS disabled or TACACS contact loss Enable URPC usernames as backup enabled user Log in OK URPC validates the user Case 4 TACACS disabled or TACACS contact loss Enable URPC usernames as backup disabled user Log in FAIL Neither TACACS nor the URPC can validate the user Parameters to determine if user should be able to log in TACACS enabled disabled Good Bad TACAC...

Страница 67: ...ch of the unit s side panel with two screws Verify both brackets are facing the same direction on the unit once attached M140R115 1U side panel 2U Bracket part number M140R114 Attach brackets to the each of the unit s side panel with two screws Verify both brackets are facing the same direction on the unit once attached M140RC114 U2 side panel Attach brackets and unit to rack with four screws as s...

Страница 68: ...C138 brackets to the Baytech vertical power strip In each unit locate the small bubble wrapped brackets containing two brackets and four screws See figure 1 and 2 Figure1 Figure2 Line up the bracket holes to the holes on the unit Figure 3 Figure 3 Screw in two screws Figures 4 5 6 show the bracket mounted in three different positions Figure 4 Figure 5 Figure 6 ...

Отзывы: