6.2
Respecting the distance between the indoor module and the outdoor unit
To ensure that the heat pump functions correctly, respect the minimum
and maximum connection lengths between the indoor module and the
outdoor unit.
1. Respect distances A, B and C between the outdoor unit 1 and the
indoor module 2.
Tab.18
A: Maximum/
minimum length
B: Maximum
height differ
ence
C: Maximum
number of el
bows
AWHP 4.5 MR 2 to 30 m
30 m
10
AWHP 6 MR-3 2 to 40 m
30 m
15
AWHP 8 MR-2 2 to 40 m
30 m
15
AWHP 11
MR-2
2 to 75 m
30 m
15
AWHP 11 TR-2 2 to 75 m
30 m
15
AWHP 16
MR-2
2 to 75 m
30 m
15
AWHP 16 TR-2 2 to 75 m
30 m
15
2. Make one or two horizontal loops with the refrigerant connections to
reduce disruption.
If the length of the refrigerant connections is less than 2 m, disruptions
can occur:
Functional disruptions caused by a fluid overload,
Noise pollution caused by the circulation of the refrigerant.
6.3
Positioning the indoor module
6.3.1
Allowing sufficient space for the indoor module
Allow sufficient space around the heat pump indoor module to ensure
adequate access and facilitate maintenance.
Fig.27
MW-M001439-2
A
B
2
1
C
Fig.28
MW-3001012-2
10
00
1200
50
0
50
0
100
6 Installation
7706696 - v04 - 11102018
AWHP-2 PBS-i
35
Содержание PBS-i WH2 Series
Страница 45: ...12 Appendix 7706698 v04 17102018 AWHP 2 PBS i 45 ...
Страница 46: ...12 Appendix 46 AWHP 2 PBS i 7706698 v04 17102018 ...
Страница 69: ...3 4 Electrical diagram Fig 12 MW 5000747 5 3 Technical specifications 7706696 v04 11102018 AWHP 2 PBS i 21 ...
Страница 154: ...12 Decommissioning and disposal 106 AWHP 2 PBS i 7706696 v04 11102018 ...
Страница 178: ...1 Spare parts 22 AWHP 2 PBS i 7706697 v04 11102018 ...