ADV parameter
Description of the ADV advanced parameters
Factory setting
EHC–06
HP069
Nominal flow rate setpoint for central heating
Can be set from 0 to 100 l/min
12 for 4.5 kW
17 for 6 kW
23 for 8 kW
HP079
Maximum offset applied to the cooling setpoint when a 0-10V humidity sensor is
used
Can be set from 0 to 15°C
5
HP086
Activation of hydraulic management mode for the configuration with a low-loss
header, or for a buffer tank connected as a low-loss header
0 =No
1 =Yes
0
HP087
Temperature hysteresis to start or stop heating the buffer tank
Can be set from 0 to 30 °C
6
HP091
Heating setpoint temperature offset when photovoltaic energy is available
Can be set from 0 to 30 °C
0
HP092
Domestic hot water setpoint temperature offset when photovoltaic energy is
available
Can be set from 0 to 30 °C
0
HP094
Start time of the heat pump low noise function
Can be set from 00:00 to 23:59
Value accepted when HP058 = 1
22:00
HP095
End time of the heat pump low noise function
Can be set from 00:00 to 23:59.
Value accepted when HP058 = 1
06:00
HP108
Activation time delays for the back-ups between stage 1 and stage 2 (electrical
back-up) in central heating mode
4
PP016
Maximum central heating pump speed (%)
Maximum pump speed in heating mode
Can be set from 20 to 100%
100%
PP018
Minimum central heating pump speed (%)
Minimum pump speed in heating mode
Can be set from 20 to 100%
30%
AD
Auto detect
available
CNF
Reset factory parameters
See the data plate
ADV
ADV advanced parameters
not available
7.3
Setting the parameters
7.3.1
Language selection
1. Access the User menu.
2. Select the HMI sub-menu.
3. Select the AP103 parameter corresponding to language selection by
pressing the or keys.
4. Confirm by pressing the
key.
Fig.90
MW
-5
0
0
0
4
0
6
-2
7 Settings
72
7654506 - v06 - 19112019
Содержание MIC V200