A disconnector
A 7 bar safety valve
An evacuation pipe
A thermostatic mixing valve
Isolation and venting valves for maintenance operations
Connecting the domestic water:
Comply with local standards and directives.
Install a water drain in the boiler room.
Use components that comply with the applicable standards and
regulations in the country concerned.
Temperature limit at the draw-off point
The maximum domestic hot water temperature at the draw-off point is
subject to special regulations in the various countries in which the
appliance is sold in order to protect the user. These special regulations
must be observed when installing the appliance.
Water operating pressure
The tanks on our domestic hot water heaters can run at a maximum
operating pressure of 1.0 MPa (10 bar). The recommended operating
pressure is under 0.7 MPa (7 bar).
5.6.3
Connecting the various circuits
The water connections are made on the connection plate.
1. Tighten the various connectors between the indoor module and the
connection plate.
5.6.4
Fitting the condensate collector box
The condensate collector box and the discharge hose are located in the
package containing the connection plate.
1. Connect the siphon to the condensate discharge hose provided.
2. Flush the box with clean water to clear any impurities from the siphon.
3. Insert the mounting lugs in the lug recesses on the box to attach the
box to the connection plate.
4. Fill the siphon.
Fig.43
MW
-3
0
0
0
6
6
5
-2
1
Fig.44
MW
-3000712-01
3
3
5 Installation
38
7654506 - v06 - 19112019