Fig. 14
Fig. 15
Fig. 15a
page 23
8.0 Flue Options
8.1 Horizontal Flue Systems
1. The standard flue is suitable only for horizontal termination applications.
2. All fittings should be fully engaged. The approximate engagement is 40 mm. Use the lubrication provided in the kit to aid assembly.
3. For long flue runs allow 5 mm per metre for expansion.
4. Maximum permissible equivalent flue lengths are: Horizontal Concentric (60/100) 5 metres
5. Any additional "in line" bends in the flue system must be taken into consideration.
Their equivalent lengths are:
Concentric Pipes:
(60/100)
135° bend 0.5 metres
93° bend 1.0 metres
The elbow supplied with the standard horizontal telescopic flue kit is not included in any equivalent length calculations
NOTE: Flue length is measured from point X to Y as shown.
IMPORTANT: All flue systems must be securely supported at least once every metre.
Suitable pipe supports are available as accessories.
Содержание ECOGEN 24/1.0
Страница 69: ...Fig 77 Fig 78 Fig 79 page 69 16 0 Schematic Wiring 16 1 Burner Control Units BCU Connections...
Страница 70: ...page 70 16 2 Milligrid 24 way Connector...
Страница 71: ...page 71 16 3 14 way Connector...
Страница 72: ...page 72 16 4 Engine Circuit...
Страница 73: ...page 73 16 5 Power Monitoring 24Vdc Power Supply...
Страница 74: ...page 74 16 6 External Connections External Wiring...
Страница 85: ...page 87...
Страница 86: ...page 88...
Страница 87: ...page 89 Section P...
Страница 88: ...page 90...
Страница 89: ...page 91 Section Q Engine developing less than 950W after 15 minutes running at maximum rate...
Страница 91: ...page 93 page 94 page 95 page 96 MICRO CHP SYSTEM COMMISSIONING CHECKLIST...
Страница 92: ...page 97...