Product information
PD-TaD 80
16 / 74
822-188-3
3.3
PD-TaD
No.
Designation
on device
Element
Function
1
–
PD measuring unit
Is used for the measurement and location of partial
discharges
2
Protective earthing
connection
Is used to connect the protective earthing
The earthing connection for the short-circuit cable is
located on the side of the protective earthing connection.
3
–
HV coupling unit with
integrated measurement
impedance
Is used to couple out high-frequency PD pulses via a
measurement impedance (in accordance with IEC 60270)
and convert them into equivalent voltage signals
4
–
Short-circuit cable
Is used to short-circuit the HV ports
HV IN
and
HV OUT
and the protective earthing (for the transportation and
storage of the PD-TaD)
5
–
Port for the short-circuit
cable
Is used to connect the short-circuit cable to the HV ports
HV IN
and
HV OUT
Two connection sockets are provided on each of the HV
connectors for the short-circuit cable: on the top and on
the side.
6
–
Handles
Are used to lift and carry the PD-TaD
7
HV OUT
HV output
Is used to connect the PD-TaD to the test object
8
HV IN
HV input
Is used to connect the PD-TaD to the VLF HV generator or
the HV connection cable of the cable drum rack
9
VLF Generator
Port
Is used to connect the PD-TaD to the VLF HV generator or
the connection box of the cable drum rack (for dissipation
factor measurement)
10
PWR
LED
Does not come on: PD-TaD is not supplied with
voltage.
Is on continuously: PD-TaD is supplied with voltage.