7.13 Analog Inputs
Function
The function module in combination with the 2 analog inputs enable the programming of 2 byte length
parameters.
Cycle time of analog inputs: 1 ms
Six parameters are assigned to each input:
–
AI input channel:
input
channel
entry
–
AI smoothing
:
smoothing time constant [ms].
–
AI scaling
:
scaling factor entry
–
AI offset
: offset
entry
–
AI threshold value
: sensitivity
of
inputs
–
AI target Pxxx
:
target parameter number entry
–
AI value
: current
output
value
.
NOTE
The sequence of the parameter setting is irrelevant. Switching is carried out as soon as the target
parameter number has been set.
The target parameter number must be reset to zero in order to deactivate an input. However, the
target parameter still contains the last output value. If AI target Pxxx is deactivated or newly set,
the parameter „AI x offset“ is additionally set to zero.
Содержание BUS 6 VC
Страница 1: ...E 5 03047 01 Manual V Controller BUS 6 VC Specification Digital Control BUC ...
Страница 4: ...Dokument Nr Document No 5 04058 01 Baumüller Nürnberg GmbH ...
Страница 8: ...6 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 14: ...Technical Data 12 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 16: ...Transportation Unpacking 14 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 92: ...Parameter 90 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 108: ...Appendix 106 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 109: ......