Parameter
V-Controller (BUS 6 VC)
71
Baumüller Nürnberg Electronic GmbH & Co. KG
5.03047.01
7.12 Set Value Generator
Function
The module creates a plateau set value for each of the 4 time zones. Both the plateau amplitude and the
output time interval per zone can be allocated parameters. The amplitudes are relative and are standar-
dised by means of the min./max. receiver values. On termination of the last time zone the first time zone
starts again. Each time the controller is enabled the set value generator is newly started in zone 1. When
leaving the state „operation enabled“ (P121), the set value generator is stopped.
Thus e.g. the following speed set value graph can be created:
Parameter overview
Parameter
Name
Range
min. ... max.
Unit
Display
only
P150
SVG
state
0000 ... FFFF
!
P140
SVG
target Pxxx
0 ... 700
P141
SVG
output
- 100,00 ... + 100,00
%
!
P142
SVG
set value 1
- 100,00 ... + 100,00
%
P143
SVG
set value 2
- 100,00 ... + 100,00
%
P144
SVG
set value 3
- 100,00 ... + 100,00
%
P145
SVG
set value 4
- 100,00 ... + 100,00
%
P146
SVG
time 1
0,001 ... 60,000
s
P147
SVG
time 2
0,001 ... 60,000
s
P148
SVG
time 3
0,001 ... 60,000
s
P149
SVG
time 4
0,001 ... 60,000
s
Содержание BUS 6 VC
Страница 1: ...E 5 03047 01 Manual V Controller BUS 6 VC Specification Digital Control BUC ...
Страница 4: ...Dokument Nr Document No 5 04058 01 Baumüller Nürnberg GmbH ...
Страница 8: ...6 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 14: ...Technical Data 12 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 16: ...Transportation Unpacking 14 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 92: ...Parameter 90 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 108: ...Appendix 106 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Страница 109: ......