Parameter
V-Controller (BUS 6 VC)
51
Baumüller Nürnberg Electronic GmbH & Co. KG
5.03047.01
P121
M
state word
This parameter corresponds to DRIVECOM object 6041
hex
and is the output word of the unit
control state machine.
Bit no.
Name
Comment
0
READY TO START
1
SWITCHED ON
2
OPERATION ENABLED,
pulses enabled
3
FAULT
4
Uzk control is enable
5
always 1
6
INHIBIT START
7...9
reserved
10
set value reached
11...15
reserved
NOTE
After enabling the controller the value of parameter P121 (state word) changes from
0x0021 to 0x0033. If the set voltage is reached the "ready for use" relay is enabled and the
parameter P121 is set to 0x0437.