Mounting the unit
Manual Single Power Unit BUM64S/A/F
Document no.: 5.01056.03
Baumüller Nürnberg Electronic GmbH & Co. KG
40
5.4
5.4.2.2 Connecting BUM64F to coolant circulation
The BUM64F unit has a pre-mounted heatsink at its back. The topmost and the lowest
threaded hole (G1/8") in the heatsink are destined for the intake and outlet of a coolant
circulation system. For the connection to the customer side of the coolant circulation use
connectors with an outside thread G1/8". Onto these connectors the customers hoses for
intake and outlet can be fitted.
The BUM64F is mounted in a switching cabinet. The heatsink connections are then situ-
ated on the back side of the unit.
Mounting the heatsink connections:
1
supply suitable connectors (material: brass, G1/8“ outside thread)
2
clean the threaded holes and connectors
3
apply silicone sealant, e.g. Loctite 5331 onto a least one (clean!) thread winding.
The silicone sealant prevents either corrosion between the different construction ma-
terials and improves also the security/tightness.
4
turn the connectors by hand into the threaded holes of the heatsink and tighten them
with the maximum admissible torque.
5
connect the intake with one of the connectors.
6
connect the outlet with the other connector.
7
check the tightness of the coolant circulation.
8
perform a leak test with the required pressure (12 bar).
CAUTION
The following
may occur
,
if you do not observe this caution information:
m
property damage.
The hazard is: damage of the connectors thread.
do not exceed the maximum torque (6 Nm) when you tighten the connectors.
NOTE
You can choose any direction of flow.