133
Operation Manual
Safety Module for b maXX 5000
BM5-O-SAF-002/3
Document no.: 5.11016.03
17
S
YSTEM
VALIDATION
All safety functions as well as the trouble-free functioning of the installed and
parameterized system must be tested with the initial operation and after changes. The
testing of the system must be documented.
WARNING!
Danger during commissioning!
The Safety Module may only be put into operation after being tested successfully by
a technical expert.
Therefore:
m
Conduct a complete function test. In doing so, check the correct allocation of the
connected safety components.
m
A checklist for the commissioning and validation of the system is reproduced in
Appendix
B.3 Commissioning and validation checklist
Conduct the validation of the system in accordance with this checklist and
document the procedure accordingly.
m
Make sure that operating personnel has been instructed in the handling of the
Safety Module.
17.1 Function test
The function test is a major part of the validation of the entire system. The function test is
used to determine the trouble-free allocation of the network safety components and the
programmed logic of the system.
Depending on the complexity of the logic circuit of the respective project, it is
recommended to conduct the function tests in steps.
The following course of action is recommended when conducting the function tests:
1
Only connect the actuators and drives to the safe output terminals once no errors have
been detected in the inspection of the logic circuit.
2
Conduct a complete function test with all sensors (initiators), switches, actuators and
drives.