![Baumuller b maXX BM5800 Скачать руководство пользователя страница 81](http://html.mh-extra.com/html/baumuller/b-maxx-bm5800/b-maxx-bm5800_parameter-manual_2711380081.webp)
Description of the Software Modules and Parameters
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
81
3
3.4.2
Motor
3.4.2.1 Motor Identification Plate
Stegmann and Heidenhain encoders provide the option of storing OEM data in their
EEPROM. This memory is used to store the following information in the encoders:
m
Notch angle offset
m
Machine characteristics
m
Encoder characteristics
m
Motor ordering code
The data structure of the OEM memory follows the Baumüller standard, as already imple-
mented on the b maXX 4400. Thus identification plates can also be read from encoders
which were previously used in b maXX 4400 drives and conversely.
3.4.2.2 Torque limits
Display maximum torque
The parameter
"Max. torque actual value" represents the maximum internal
torque of the motor M
max act
and is proportional to the maximum torque current I
sq max
.
with
I
sq max
Maximum torque current in A: "Max. torque current actual value"
Flux
set
Magnetic flux set value in %
Kt
upd
Kt
The maximum torque current I
sq max
is calculated from the "Max. drive current actual val-
ue"
I
max act
and with subtraction of the field current. The "Max. drive current actual
value"
in general is the same as the maximum drive current
. However,
this current and the actual maximum torque can be reduced by the power unit overload
monitoring (refer to "Bit mask of external drive current limit"
NOTE!
is set to zero, then the torque limit is suspended. This state
is achieved by setting the Nominal power
to 0 kW. If the Kt correction factor
is set to zero, then the torque limit limits the torque current to 0 A.
M
max act
I
sq max
Kt
upd
Flux
set
[%]
=
Содержание b maXX BM5800
Страница 10: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 10 of 814 Contents ...
Страница 724: ...Monitoring Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 724 of 814 3 11 ...
Страница 756: ...Error descriptions Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 756 of 814 4 5 ...
Страница 800: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 800 of 814 ...
Страница 808: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 808 of 814 ...
Страница 814: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 814 of 814 Notes ...
Страница 815: ......