Operating Modes
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
582
3.8
120.16
Homing max. position delta to zero pulse
This parameter determines the maximum distance, which is moved from the last switch-
ing edge until zero pulse is detected. If the zero pulse is not detected within this distance,
"Homing" error no. 901 is reported and homing is interrupted.
This function is deactivated, if the value is 0. There is no distance monitoring until to the
zero pulse.
Display: 65536 increments correspond to 1 revolution.
120.17
Command
Homing command. Via this parameter the setting of a reference point is possible in the
inhibited state.
Value
Meaning
0
No command / reset
The acknowledgment bit of „Set reference point“ (
bit 2) is deleted.
1
Set reference point
The positioning value at the current position is set to the reference point
value.
Содержание b maXX BM5800
Страница 10: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 10 of 814 Contents ...
Страница 724: ...Monitoring Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 724 of 814 3 11 ...
Страница 756: ...Error descriptions Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 756 of 814 4 5 ...
Страница 800: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 800 of 814 ...
Страница 808: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 808 of 814 ...
Страница 814: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 814 of 814 Notes ...
Страница 815: ......