Safe stop
Instruction handbook
b maXX
BM4400, BM4600, BM4700
Document No.: 5.12008.07
351
E
Single safety relay:
1)
Customer-specific versions, only.
Contact Baumüller Nürnberg GmbH before using this version.
2)
A switching current of at least 20 mA is recommended. If the load is below 20 mA the switching current must be in-
creased by a base load (see
Double safety relay:
1)
Customer-specific versions, only.
Contact Baumüller Nürnberg GmbH before using this version.
2)
A switching current of at least 20 mA is recommended. If the load is below 20 mA the switching current must be in-
creased by a base load (see
BM4XXX-XX
1
-XXXXX-S01
Single
safety relay module with
high power current contacts
BM4XXX-XX
3
-XXXXX-S01
Single
safety relay module with
low power current contacts
1)
BM4XXX-XX
5
-XXXXX-S01
Single
safety relay module
Elestra
Coil side, Triggering of one safety relay (X102-3, X102-4)
Rated voltage U
DC
24 V
24 V
24 V
Operating voltage range
-15% / +20%
-15 % / +20 %
-15% / +20%
Control current I
DC
max. 70 mA
max. 70 mA
max. 35 mA
Feedback contact, 1 x NC contact (X102-1, X102-2)
Switching voltage U
DC
24 V
24 V
24 V
Switching current I
DC
10 mA to 4 A
2)
10 mA to 300 mA
2)
10 mA to 4 A
2)
Switch-on frequency
max. 6/min
max. 10/s
max. 12/s
Activation delay time at rated voltage U
DC
max. 25 ms
max. 15 ms
max. 15 ms
Deactivation delay time
max. 15 ms
max. 12 ms
max. 12 ms
Electrical endurance
at least 10
5
operating cycles
at least 10
5
operating cycles
at least 10
5
operating cycles
Mechanical service life
at least 1 x 10
7
switching cycles
at least 5 x 10
7
switching cycles
at least 1 x 10
7
switching cycles
BM4XXX-XX
2
-XXXXX-S01
Double
safety relay module with
high power current contacts
BM4XXX-XX
4
-XXXXX-S01
Double
safety relay module with
low power current contacts
1)
BM4XXX-XX
6
-XXXXX-S01
Double
safety relay module
Elestra
Coil side, input signal of two safety relays (X102-3, X102-4) (X103-3, X103-4)
Rated voltage U
DC
24 V
24 V
24 V
Operating voltage range
-15% / +20%
-15 % / +20 %
-15% / +20%
Control current I
DC
max. 70 mA
max. 70 mA
max. 35 mA
Feedback contact, 1 x NC contact (X102-1, X102-2) (X103-1, X103-2)
Switching voltage U
DC
24 V
24 V
24 V
Switching current I
DC
10 mA to 4 A
2)
10 mA to 300 mA
2)
10 mA to 4 A
2)
Switch-on frequency
max. 6/min
max. 10/s
max. 12/s
Activation delay time at rated voltage U
DC
max. 25 ms
max. 15 ms
max. 15 ms
Deactivation delay time
max. 15 ms
max. 12 ms
max. 12 ms
Electrical endurance
at least 10
5
operating
cycles
at least 10
5
operating cycles
at least 10
5
operating
cycles
Mechanical service life
at least 1 x 10
7
switching
cycles
at least 5 x 10
7
switching
cycles
at least 1 x 10
7
switching
cycles