Requirements for the motor temperature sensors
Instruction handbook
b maXX
BM4400, BM4600, BM4700
Document No.: 5.12008.07
Baumüller Nürnberg GmbH
170
7.8
In order to have EMC-compliant and problem-free use within the framework of the legis-
lation, the following aspects must be taken into account.
In case of any questions, please contact Sales or the Applications department of
Baumüller Nürnberg GmbH.
m
Only use Baumüller motor cables and Baumüller components.
m
Use suitable mains filters from Baumüller Nürnberg GmbH.
m
Mount all components on a single mounting plate with a continuously good electrically-
conductive surface (e.g. galvanized steel plate).
m
Keep the ground connection device/ground plate as short as possible (< 30 cm) , using
fine-stranded cables with a large cross-section (>10 mm
2
).
m
When installing, be sure to follow the correct sequence:
power supply system - fuse - filter - choke - (ferrite core) -
BM4400, BM4600, BM4700
- (motor filter) - motor.
m
Ensure that the motor cable is continuous, without interruption.
Do not interrupt motor cables with terminals, contactors or fuses, for example.
m
Route the cables directly on the surface of the grounded mounting plate.
(smallest possible effective aerial height).
m
When routing in parallel, maintain a minimum clearance of 20 cm between signal and
control cables vis-à-vis the power cables.
m
Cross cables with different EMC categories (signal cables - supply cables or motor ca-
bles) only in a 90° angle.
m
Contact the major cable shield when laying cables through walls, which separate dif-
ferent EMC areas.
m
Contact all the cable’s shields on both sides surface-to-surface and also well-conduc-
tive with ground.
7.8
Requirements for the motor temperature sensors
Type
Additional requirements:
Isolation
KTY84
-
SELV/PELV
MSKL
1)
(PTC)
R = 1 k
at T
threshold
, I
max
< 2 mA
SELV/PELV
To protect the motor against not permitted overheating, a motor temperature sensor can
be connected to the
b maXX
device. The device switches off of the motor when a settable
threshold temperature has been exceeded.
1)
Motor protection resistor (PTC) as per DIN 44080-082
NOTE!
The motor temperature sensor should be installed in such a manner that „safe elec-
trical separation“ is ensured. The motor temperature sensors integrated into
Baumüller motors meet these requirements. If third-party motors are connected, the
proprietor must ensure that the temperature sensors used in the motor of a third-party
manufacturer motor comply with the „safe electrical separation“ function.