Controllers
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
Baumüller Nürnberg GmbH
514
4.7
The absolute two-level controller switches on, if the following is valid:
Parameter number actual value
lower absolute switching threshold
151.15
Upper threshold absolute UDINT
If the data type of the parameter selected with
is INT, DINT, UINT, UDINT,
WORD or DWORD, then this parameter forces the upper absolute switching threshold.
The absolute two-level controller switches off, if the following is valid:
Parameter number actual value
upper absolute switching threshold
4.7.5.9 Description of the Two-level Controller Parameter with relative and absolute Thresholds
152.1
Mode
Configuration of the relative two-level controller
152.2
Status
State of the relative two-level controller
Bit
Meaning
0
0: Comparison actual value to absolute thresholds inactive
1: Comparison actual value to absolute thresholds active
1
0: Comparison actual value to relative thresholds inactive
1: Comparison actual value to relative thresholds active
2
0: No absolute-value generation at actual value (comparison signed)
1: Absolute-value generation at actual value (symmetrical monitoring)
15 … 3
Reserved
Bit
Meaning
0
Status indication of the entire two-level controller
0: Output inactive
1: Output active
1
Status indication of the absolute two-level controller
0: Output absolute two-level controller inactive
1: Output absolute two-level controller active