Description of the Software Modules and Parameters
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
105
4
After the phase error delay time has elapsed, if the phase failure condition still exists
the drive generates Error 1015 "Phase error timeout" and inhibits the pulses to the
power unit.
If the phase error is cleared during phase error delay time, the controller deletes the
warning and switches back to the non-reduced current operation.
m
Active braking („Return motion“, „Stop (Ramp-down time)“, „Stop (Quick stop time)“,
„Stop at current limit“, „Controlled stop“, „SS1 stop“)
The drive effects an active error response, changes to „failure“ state upon comple-
tion and inhibits the pulses to the power unit.
If the error response will be not finished up to the phase error delay time has
elapsed, the drive generates Error 1015 "Phase error timeout" and inhibits the puls-
es to the power unit.
Also if the phase error is cleared during phase error delay time, the pulses to the
power unit will be inhibited finally.
m
Pulse block
This response is not permitted. In order that the pulses are inhibited fast as possible,
the parameter
>
130.24
<
is set to 0.
If Bit 2 of parameter
Mode is not set, the phase error delay time doesn’t act.
This parameter is
not
available at
BM2500
.
130.25
Mains failure delay
A mains failure is ignored within this time.
Warning 1046 Mains failure is generated in general if a mains failure is detected. If the
mains failure is longer than the Mains failure delay and if the drive was enabled at the be-
ginning, an error message is generated (error 1016 Mains failure or error 1032 Error DC-
link supply).
Different options are possible for the behavior during the Mains failure delay. This options
are defined in parameter
Mode.
If the mains is available again within the set Mains failure delay, no error message is gen-
erated. The warning is deleted and normal operation is continued.
130.29
Chopper threshold
The chopper resistor is switched on if the DC-link voltage reaches the parameterized
chopper threshold. The chopper resistor is switched off if the DC-link voltage decreases
to at least 20 V.
130.34
Status STO module
This parameter indicates the status of the STO module. If STO is triggered, the error bits
indicate the cause for the triggering.
The parameter should only be requested at disabled drive, because timeout errors (see
bit 0) could occur at enabled drive.