Operating conditions
Instruction handbook
b maXX
5000
Document No.: 5.09021.16
Baumüller Nürnberg GmbH
44
3.3
3.3
Operating conditions
3.3.1
Requirements for power supply / mains supply system
Power supply mains
BM50XX - X
T
XX / - X
R
XX
6)
BM51XX - X
T
XX / - X
R
XX
6)
Industrial system, with direct or low
impedance grounded neutral point
(TN system or TT system)
BM50XX - X
I
XX /
- X
S
XX
Industrial system with not grounded or with
high impedance grounded neutral point
(IT system)
in addition TN or TT system
BM50XX -
X
G
XX / - X
W
XX
Industrial system, with direct or low
impedance grounded junction of phases
(grounded delta wye)
in addition TN system, TT or IT system
Inductance
(sum of mains inductance
and mains choke inductance)
BM50XX - X
T
.../X
I
.../X
G
...
BM51XX - X
T
.../X
I
.../X
G
...
u
k min
= 2.4 %
u
k max
= 4 %
Mains inductance
7)
BM503X -
X
R
.../X
S
.../X
W
...
BM504X -
X
R
.../X
S
.../X
W
...
u
k min
= 0.5 %
Rated power supply voltage/frequency
1) 2)
(U
AC
) device
3 x 400 V
50/60 Hz
Power supply voltage
Absolute minimum
1) 2)
(U
AC
) device
Absolute maximum
1) 2)
(U
AC
) device
BM50XX
3 x 207 V
/ 50/60 Hz
3 x 528 V / 50/60 Hz
BM51XX
3 x 360 V
/ 50/60 Hz
3 x 528 V / 50/60 Hz
Absolute frequency minimum
5)
Absolute frequency maximum
5)
47 Hz
63 Hz
Overvoltage category
EN 61800-5-1, chapter 4.3.6
III
Harmonic frequencies (power supply voltage)
EN 61800-3, chapter 5.2.1, class 3
THD
U
b
12 %
Power supply voltage asymmetry
EN 61000-2-4, table 1, Class 3
Max. 3 %
Commutation notches
EN 61800-3, chapter 5.2.1, class 3
Notch depth < 40 %,
area < 250 % x degree
Voltage drops
EN 61800-3:2004 and A1:2012
10 % to 80 %
1)
Voltage changes/fluctuation
EN 61200-2-4, class 3
+/-10 %
+10 % to -15 %, for a duration of
b
1 min
Max. short circuit current power supply
4)
50 000 A
Control voltage
3)
(U
DC
)
according to EN 61131-2:2008
+ 24 V -15 % / +20 %
Содержание b maXX 5000
Страница 101: ...Design and Operation Instruction handbook b maXX 5000 Document No 5 09021 16 101 of 328 4 ...
Страница 220: ...Fieldbus communication Instruction handbook b maXX 5000 Document No 5 09021 16 Baumüller Nürnberg GmbH 220 of 328 8 4 ...
Страница 240: ...Error handling Instruction handbook b maXX 5000 Document No 5 09021 16 Baumüller Nürnberg GmbH 240 of 328 10 4 ...
Страница 298: ...Instruction handbook b maXX 5000 Document No 5 09021 16 Baumüller Nürnberg GmbH 298 of 328 A ...
Страница 299: ...299 of 328 Operation Manual b maXX 5000 Document no 5 09021 16 APPENDIX B DECLARATION OF CONFORMITY ...
Страница 324: ...Instruction handbook b maXX 5000 Document No 5 09021 16 Baumüller Nürnberg GmbH 324 of 328 Table of Figures ...
Страница 328: ...Instruction handbook b maXX 5000 Document No 5 09021 16 Baumüller Nürnberg GmbH 328 of 328 Notes ...
Страница 329: ......