PLCopen motion control
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
201
B.3.4
Parameters and handling
m
Error System
Error System
m
Control word
6040
hex
= P0300 (b maXX
®
1000 parameter)
Control word used in the status machine of the unit control
1
)
:
these Bits are low-active.
NAME
Index
Sub-index
Data type
Access
type
Default value
Error System
40C8
hex
00
hex
U32
RO
0
hex
Bit-No.
Meaning
Error name
Reaction
10
Error in drive manager
SYS_ERR_DRIVE_
MANAGER
adjustable
NAME
Index
Sub-index
Data type
Access type
Default
value
Control word
6040
hex
00
hex
U16
RW
0
hex
Bit-No.
Meaning
0
1: Command „switch on“
0: Command „shut down“
1
1)
1: Command „inhibit
no
voltage“ (operating status)
0: Command „inhibit voltage“
2
1)
1: Command „
no
quickstop“ (operating status)
0: Command „quickstop“
3
1: Command „operation enabled“
0: Command „inhibit operation“
4
Ramp function generator Inhibit
1)
: output frequency fixed to 0
5
Ramp function generator Stop
1)
: freeze output frequency
6
Ramp function generator Zero
1)
: set output frequency by ramp to 0
7
0 to 1 : reset error
8-15
Reserved
Содержание b maXX 1000
Страница 1: ...E 5 07004 03 b maXX 1000 Parameter manual ...
Страница 65: ...Parameter Parameter manual b maXX 1000 Document no 5 07004 03 65 of 208 4 Figure 18 Base block speed search ...
Страница 164: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 164 of 208 A ...
Страница 208: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 208 of 208 Notes ...
Страница 209: ......