B.2.1
The CANopen address in case SWITCH VALUE > 0
P0870 (CANopen address) reads the value only from CAN with switch address parameter (P2141 … P2147)
x P2148, if P2148 = 0 then P0870 reads the value only from parameter (P2141 … P2147) and P0871 (CANo-
pen baud rate) reads the value from Parameter P2140.
m
CAN with switch address if switch value multiplications parameter P2148 > 0
m
CAN with switch address if switch value multiplications parameter P2148 = 0
B.2.2
The value for CANopen address in case SWITCH VALUE = 0
P0870 (CANopen address) and P0871 (CANopen baudrate) can be entered by the user directly.
CANopen is deactivated, if the P0870 (CANopen address) is 0.
Switch
value
Switch value multi-
plication P2148
default
CAN
switch address
Switch address baud rate parameter
P2140
Parameter
Value
Default
Value
1
8
P2141
1
2
0: 1000k
2
8
P2142
2
1: 500k
3
8
P2143
3
2: 250k
4
8
P2144
4
3: 125k
5
8
P2145
5
4: 100k
6
8
P2146
6
5: 50k
7
8
P2147
7
Switch
value
Switch value multi-
plication P2148
default
CAN
switch address
Switch address baud rate parameter
P2140
Parameter
Value
Default
Value
1
0
P2141
21
2
0: 1000k
2
0
P2142
22
1: 500k
3
0
P2143
23
2: 250k
4
0
P2144
24
3: 125k
5
0
P2145
25
4: 100k
6
0
P2146
26
5: 50k
7
0
P2147
27
b maXX
®
1000 parameter no.
Default value
Value
P0870 (CANopen address)
1
0 to 127
P0871 (CANopen baudrate)
0
0
0: 1000k
1
1: 500k
2
2: 250k
3
3: 125k
4
4: 100k
5
5: 50k
Содержание b maXX 1000
Страница 1: ...E 5 07004 03 b maXX 1000 Parameter manual ...
Страница 65: ...Parameter Parameter manual b maXX 1000 Document no 5 07004 03 65 of 208 4 Figure 18 Base block speed search ...
Страница 164: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 164 of 208 A ...
Страница 208: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 208 of 208 Notes ...
Страница 209: ......