en_BA_OM70_multi-spot.docx
27/60
Baumer Electric AG
04.01.2021 14:26/tof V1.2 ANW_81156398
Frauenfeld, Switzerland
5.8
ANALOG OUT
5.8.1
SCALE OUT
In the factory setting, the analog output runs across the entire measuring range (start of measuring range Sdc
-
end of measuring range Sde) from 0...10V (voltage mode) or from 4...20mA (current mode).
The start and end of the measuring range can be reset with SCALE OUT, reducing the measuring field and
changing the calibration curve.
The smaller measuring field improves
the measurement repetition time, ie, the measuring frequency is
increased.
*The minimum window size (distance from end of the measuring range Sde - start of measuring range Sdc)
must be greater than 5% of the "end of measuring range" value.
5.8.1.1
DIST NEAR
The value in mm at which the sensor should have the
minimum analog output value of 0V or 4 mA is
specified here.
DIST NEAR >= Start of measuring range
DIST NEAR <= End of measuring range – minimum
window size*
5.8.1.2
DIST FAR
The value in mm at which the sensor should have the
maximum analog output value of 10V or 20 mA is
specified here.
DIST FAR <= End of measuring range
DIST FAR >= Start of measuring range + minimum
window size*
Current Start of
measuring range Sdc
0 V
4 mA
10 V
20 mA
DIST.
NEAR
DIST.
FAR
Scaled measuring
range
Current End of
measuring range Sde
NOTE
The measuring cycles can be shortened by reduction of the window size, i.e. this
increases the measuring frequency, according to data sheet chapter 6.1.
Start of measuring
range
Sensor level R2 =
reference
*Minimum
window size
*
End of measuring
range